Proline Promag 10D
10
Hauser
Installation
Mounting location
The sensor should preferably be installed in an ascending pipe. Ensure the sensor is an adequate distance
(
2 × DN) away from the next pipe bend.
!
Note!
Entrained air or gas bubble formation in the measuring tube can result in an increase in measuring errors.
For this reason, the following mounting locations should be
avoided
:
• Highest point of a pipeline. Risk of air accumulating!
• Directly upstream from a free pipe outlet in a vertical pipeline. Risk of pipe not filling correctly!
A0010705
Mounting location
Orientation
h
2 x DN
³
Vertical
Horizontal
Vertical orientation is generally preferred. Vertical
orientation helps avoid gas and air accumulations and
deposits in the measuring tube.
A0010709
Vertical orientation
The measuring electrode axis should be horizontal in the
case of horizontal orientations. This prevents brief
insulation of the two measuring electrodes by entrained
air bubbles.
A0010710
Horizontal orientation
1
Measuring electrodes for signal detection
A
A
1