PROline Promag 10
10 Technical data
Hauser
77
10
Technical data
10.1
Technical data at a glance
10.1.1
Application
•
Measuring the flow rate of fluids in closed piping systems.
•
A minimum conductivity of
≥
50
µ
S/cm is required for measuring
•
Applications in measuring, control and regulation technology.
!
Note!
For liner specific applications see Section 10.1.2, "Function and system design"
10.1.2
Function and system design
Measuring principle
Electromagnetic flow measurement on the basis Faraday’s law.
Measuring system
The measuring system consists of a transmitter and a sensor.
Two versions are available:
•
Compact version:
Transmitter and sensor form a single mechanical unit.
•
Remote version:
Sensor is mounted separate from the transmitter.
Transmitter:
•
Promag 10
Sensor:
•
Promag W, DN 25...600 / 1/2"...24"
– Polyurethane-liner for water and waste water applications, applications with stable
and constant temperature and applications with small abrasion (e.g. mining
industry).
– Hard rubber liner for all water applications (especially potable water applications).
•
Promag P, DN 25...300 / 1/4"...24"
– PTFE-liner for all standard applications in the chemical and process industry.
•
Promag H, DN 2...100 / 1/12"...1/2"
– PFA-liner for all applications in the chemical, process and food industry. Especially
for applications with high temperatures and big temperature steps (e.g. CIP and
SIP).
10.1.3
Input
Measured variable
Flow rate (proportional to induced voltage)
Measuring range
Typically v = 0.01...10 m/s with the specified measuring accuracy
Operable flow range
Over 1000 : 1