Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
121
Response time
Navigation
Expert → Output → Curr.output 1 to n → Response time (0378–1 to n)
Prerequisite
One of the following options is selected in the
Assign curr.
• Mass flow
• Volume flow
• Correct.vol.flow
• Target mass flow
• Carrier mass fl.
• Density
• Ref.density
• Concentration
• Temperature
• Carr. pipe temp.
• Electronic temp.
• Osc. freq. 0
• Osc. ampl. 0
• Freq. fluct. 0
• Osc. damping 0
• Osc.damp.fluct 0
• Signal asymmetry
• Exc. current 0
Detailed description of the options
Oscil. frequency, Oscil. amplitude, Oscil.
damping
and
Signal asymmetry
:
Value 1 display
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Displays the response time. This specifies how quickly the current output reaches the
measured value change of 63 % of 100 % of the measured value change.
User interface
Positive floating-point number
Additional information
Description
The response time is made up of the time specified for the following dampings:
• Current output damping → 120
and
• Depending on the measured variable assigned to the output.
– Flow damping
or
– Density damping
or
– Temperature damping
*
Visibility depends on order options or device settings