Commissioning
Proline 200 HART
40
Hauser
8.7.3
Gas applications
For accurate mass or corrected volume measurement, it is recommended to use the
pressure-/temperature-compensated sensor version. If this sensor version is not
available, read in the pressure via the current input/HART. If neither of these two
options is possible, the pressure can also be entered as a fixed value in the
Fixed process
pressure
parameter.
Flow computer available only with the order code for "Sensor version", option "mass"
(integrated temperature measurement)" or option "mass (integrated pressure/
temperature measurement)".
Single gas
Combustion gas, e. g. methane CH
4
Select medium
Navigation:
Setup → Medium selection
1. Call up the
Medium selection
wizard.
2. In the
Select medium
parameter, select the
Gas
option.
3. In the
Select gas type
parameter, select the
Single gas
option.
4. In the
Gas type
parameter, select the
Methane CH4
option.
Configuring fluid properties
Navigation:
Setup → Advanced setup → Medium properties
5. Call up the
Medium properties
submenu.
6. In the
Reference combustion temperature
parameter, enter the reference combustion
temperature of the fluid.
7.
Configuring the current output
8. Configure the current output for the "energy flow" process variable.
Configuring optional fluid properties for output of corrected volume flow
Navigation:
Setup → Advanced setup → Medium properties
9. Call up the
Medium properties
submenu.
10. In the
Reference pressure
parameter, enter the reference pressure of the fluid.
11. In the
Reference temperature
parameter, enter the reference temperature of the fluid.