Integration into a PROFIBUS network
Micropilot FMR53, FMR54 PROFIBUS PA
24
Hauser
7.2.1
Hardware addressing
1. Set switch 8 to the "OFF" position.
2. Using switches 1 to 7, set the address as indicated in the table below.
The change of address takes effect after 10 seconds. The device is restarted.
Switch
1
2
3
4
5
6
7
Value in
"ON"
position
1
2
4
8
16
32
64
Value in
"OFF"
position
0
0
0
0
0
0
0
2
98
3
4
5
6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
10
Example of hardware addressing; switch 8 is set to the "OFF" position; switches 1 to 7 define the
address.
7.2.2
Software addressing
1. Set switch 8 to "ON".
2. The device restarts automatically and reports the current address (factory setting: 126).
3. Configuring the address via the operating menu: Setup → Device address
2
98
3
4
5
6
7
8
1
DIP
ON
A0015903
11
Example of software addressing; switch 8 is set to the "ON" position; the address is defined in the
operating menu (Setup → Device address).