Micropilot FMR53, FMR54 PROFIBUS PA
Integration into a PROFIBUS network
Hauser
23
6.2.4
Closing the cover of the connection compartment
1.
2.
2,5 Nm
3 mm
A0021491
1. Screw down the cover of the connection compartment.
2. Turn the securing clamp 90 ° in the clockwise direction and, using an Allen key (3 mm),
tighten the screw of the securing clamp on the connection compartment cover with
2.5 Nm.
7
Integration into a PROFIBUS network
7.1
Overview of device master file (GSD)
Manufacturer ID
17 (0x11)
Ident number
0x1559
Profile version
3.02
GSD file
Information and files available at:
•
www.endress.com
•
www.profibus.org
GSD file version
7.2
Setting the device address
2
98
3
4
5
6
7
8
1
D
IP
O
N
A0015686
9
Address switch in the connection compartment