Levelflex FMP56, FMP57 PROFIBUS PA
Commissioning
Hauser
27
8.3
Device configuration
8.3.1
Configuring level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0012838
11
Configuration parameters for level measurement in bulk solids
LN = Probe length
R = Reference point of measurement
D = Distance
E = Empty calibration (= zero point)
L = Level
F = Full calibration (= span)
1.
Setup → Device tag
Enter device tag.
2.
Setup→ Device address
Enter the device bus address (only if the address is set via the software).
3.
Setup → Distance unit
Select the length unit.
4.
Setup → Bin type
Select bin type.
5.
Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
6.
Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).