Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
Commissioning
Hauser
29
6.
Setup → Tube diameter
(only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
7.
Setup → Medium group
Specify the medium group (
Others
or
Water based (DC >= 4)
)
8.
Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
9.
Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
10.
Setup → Level
Displays the measured level L (for verification purposes).
11.
Setup → Distance
Displays the distance D between the reference point R and the level L (for
verification purposes).
12.
Setup → Signal quality
Displays the signal quality of the analyzed level echo (for verification purposes).
13.
Setup → Mapping → Confirm distance
Compare the distance displayed with the actual value in order to start recording an
interference echo map
.
2)
In the case of FMP54 with gas phase compensation (product structure: feature 540 "Application packages", option
EF or EG), mapping cannot be performed