Electrical connection
Levelflex FMP50 PROFIBUS PA
16
Hauser
2
1
3
4
A0011175
4
Pin assignment of M12 plug
1
2
Not assigned
3
Signal -
4
Ground
6.1.3
Supply voltage
PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; output"
"Approval"
Terminal voltage
E:
2-wire; FOUNDATION
Fieldbus, switch output
G:
2-wire; PROFIBUS PA,
switch output
• Non-hazardous
• Ex nA
• Ex nA[ia]
• Ex ic
• Ex ic[ia]
• Ex d[ia] / XP
• Ex ta / DIP
• CSA GP
9 to 32 V
• Ex ia / IS
• Ex ia + Ex d[ia] / IS + XP
9 to 30 V
1)
Feature 020 in the product structure
2)
Feature 010 in the product structure
3)
Input voltages up to 35 V do not destroy the device.
Polarity-dependent
No
FISCO/FNICO compliant
according to IEC 60079-27
Yes
6.1.4
Overvoltage protection
See Operating Instructions.