Tankside Monitor NRF81
Operating menu
Hauser
149
Additional information
DIO
DIO
2/4
2/4
1/3
+
+
_
_
2/4
1/3
1/3
A
C
DIO
B
A0033028
47
Operating mopdes of the Digital I/O module
A
Input passive
B
Input active
C
Output passive
Digital input source
Navigation
Setup → Advanced setup → Input/output → Digital Xx-x → Digital input source
Prerequisite
Operating mode (→ 148)
Output passive
Description
Defines which device state is indicated by the digital output.
Selection
• None
• Alarm x any
• Alarm x High
• Alarm x HighHigh
• Alarm x High or HighHigh
• Alarm x Low
• Alarm x LowLow
• Alarm x Low or LowLow
• Digital Xx-x
• Pri. Modbus x
• Sec. Modbus x
Factory setting
None
Additional information
Meaning of the options
•
Alarm x any
,
Alarm x High
,
Alarm x HighHigh
,
Alarm x High or HighHigh
,
Alarm x
Low
,
Alarm x LowLow
,
Alarm x Low or LowLow
The digital output indicates if the selected alarm is currently active. The alarms
themselves are defined in the
Alarm 1 to 4
submenus.
•
Digital Xx-x
The digital signal present at the digital input
Xx-x
is passed through to the digital
output.
•
Pri. Modbus x
in preparation
•
Sec. Modbus x
in preparation
6)