Electrical connection
Nivotester FTL325P, 3-channel
14
Hauser
6.2.2
Connecting the sensor
1
2
7
+
–
37
8
38
33
34
A0039153
8
Connecting the sensor to the Nivotester
Connectable sensors:
• Liquiphant FTL51B/62/64 with FEL67
• Liquiphant M FTL50(H), FTL51(H), FTL51C with FEL57
• Liquiphant S FTL70/71 with FEL57
• Soliphant M FTM50, FTM51, FTM52 with FEM57
Blue terminal blocks at top for hazardous area
• Twin-core connecting cable between the Nivotester and sensor, e. g. commercially
available instrument cable or cores in a multi-core cable for measurement purposes
• Use a shielded cable in the event of increased electromagnetic interference, e. g. from
machines or radio equipment. Only connect the shield to the grounding terminal in the
sensor. Do not connect it to the Nivotester.
6.2.3
Connecting the signal and control systems
Gray terminal blocks at bottom for the non-hazardous area
Relay function depending on the level and safety mode
If a device with high inductance is connected (e. g. contactor, solenoid valve), a spark
arrestor must be installed to protect the relay contact .
6.2.4
Connecting the supply voltage
Green terminal block at bottom
A fuse is integrated into the power supply circuit. An additional fine-wire fuse is not
necessary. The Nivotester is equipped with reverse polarity protection.