Commissioning
Nivector FTI26
20
Hauser
0
10
25
30
1.5Hz
rd/gn
5
3Hz
rd/gn
20
1.5Hz
rd/gn
t/s
A
B
C
A0036914
A
Remove the magnet now for full adjustment.
B
Remove the magnet now for empty adjustment.
C
Remove the magnet now to reset to factory settings.
7.5.4
Function test
Carry out a function test while the device is in operation.
‣
Hold the test magnet against the marking on the housing for at least 2 seconds.
This inverts the current switch status, and the yellow LED changes state. When the
magnet is removed, the switch status valid at that time is adopted.
If the test magnet is held against the marking for ≥ 30 seconds, the red LED will flash: The
device returns automatically to the current switch status.
The test magnet is included in the scope of delivery. It can be canceled optionally.
N
Ser
. no.:
Order code:
Ext. ord. cd.:
A0035882
11
Position for test magnet on housing nameplate
Summary of Contents for Nivector FTI26
Page 27: ......