Operating menu
Micropilot NMR84
140
Hauser
Option
Current range
for process
variable
Minimum
value
Lower alarm
signal level
Upper alarm
signal level
Maximum
value
4...20 mA US
(3.9...20.8 mA)
3.9 to 20.8 mA
3.5 mA
< 3.6 mA
> 21.95 mA
22.0 mA
Fixed current
Constant current, defined in the
Fixed current
In the case of an error, the output current assumes the value defined in the
Failure
mode
Fixed current
Navigation
Setup → Advanced setup → Input/output → Analog I/O → Fixed current
Prerequisite
Current span (→ 139)
=
Fixed current
Description
Defines the fixed output current.
User entry
4 to 22.5 mA
Factory setting
4 mA
Additional information
Read access
Operator
Write access
Maintenance
Analog input source
Navigation
Setup → Advanced setup → Input/output → Analog I/O → Analog source
Prerequisite
•
=
4..20mA output
or
HART slave +4..20mA output
•
≠
Fixed current
Description
Defines the process variable transmitted via the AIO.
Selection
• None
• Tank level
• Tank level %
• Tank ullage
• Tank ullage %
• Measured level
• Distance
• Displacer position
• Water level
• Upper interface level
• Lower interface level
• Bottom level
• Tank reference height
• Liquid temperature
• Vapor temperature
Summary of Contents for Micropilot NMR84
Page 255: ......
Page 256: ...www addresses endress com 71545626 71545626 ...