Micropilot M FMR 231 with HART/4...20 mA
Wiring
E Hauser
21
4
Wiring
4.1
Quick wiring guide
Wiring in F12/F23 housing
L00-FMR2xxxx-04-00-00-en-013
1 2
3 4
EN
DR
ES
S+
HA
US
ER
HA
USER
#
4
5
7
6
2
3
1
-
-
Ser.-No.:
Order Code:
D00882-A
U 16 ... 30 V DC
4...20 mA
t >85°C
x = if modification
see sep. label
Dat./Insp.:
PN max.
TAntenne max.
°C
79689
Maulburg
Made
in
Germany
T >70°C :
A
MICROPILOT M
HAUSER
PTB 00 ATEX
II 1/2 G EEx ia IIC T6
IP65
x x x x x x x x
x x x x x x x x
1
3
4
11
8
7
"
3 4
I+
I-
1 2
L- L+
4...20 mA
Sealed terminal
compartment
Before connection please note the following:
The power supply must be identical to the data on the
nameplate (1).
Switch off power supply before connecting up the device.
Connect Equipotential bonding to transmitter ground terminal
before connecting up the device.
Tighten the locking screw:
It forms the connection between the antenna and the housing
ground potential.
●
●
●
●
When you use the measuring system in hazardous areas, make sure you comply with
national standards and the specifications in the safety instructions (XA’s).
Make sure you use the specific cable gland.
On devices supplied with a certificate, the explosion protection
is designed as follows:
Housing F12/F23 - EEx ia:
Power supply must be intrinsically safe.
The electronics and the current output are galvanically
separated from the antenna circuit.
●
●
Unplug display connector!
Caution!
Commubox
FXA 191
DXR 375
communication
resistor
(> 250
)
Ω
alternatively
plant
ground
test sockets
(output current)
power
Connect up the Micropilot M as follows:
Unscrew housing cover (2).
Remove any display (3) if fitted.
Remove cover plate from terminal compartment (4).
Pull out terminal module slightly using pulling loop.
Insert cable (5) through gland (6).
A standard installation cable is sufficient if only the analogue signal is
used. Use a screened cable when working with a superimposed
communications signal (HART).
Only ground screening of the line (7) on sensor side.
Make connection (see pin assignment).
Re-insert terminal module.
Tighten cable gland (6).
Tighten screws on cover plate (4).
Insert display if fitted.
Screw on housing cover (2).
Switch on power supply.
●
●
●
●
●
●
●
●
●
●
●
●