Micropilot FMR67
Hauser
V. 1, Rev. 3, 11-04-2017
11
Galvanic isolation
All circuits for the outputs are galvanically isolated from each other.
Protocol-specific data
HART
Manufacturer ID
17 (0x11)
Device type ID
0x112B
HART specification
7.0
Device description files (DTM, DD)
Information and files under:
•
www.endress.com
•
www.fieldcommgroup.org
HART load
min. 250 Ω
HART device variables
The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Electronic temperature
• Terminal voltage
• Relative echo amplitude
• Absolute echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Supported functions
• Burst mode
• Additional transmitter status
Wireless HART data
Minimum start-up voltage
16 V
Start-up current
3.6 mA
Start-up time
65 s
Minimum operating voltage
14.0 V
Multidrop current
4.0 mA
Set-up time
15 s