Installation
Micropilot FMR51, FMR52 FOUNDATION Fieldbus
34
Hauser
6.7
Vessels with heat insulation
1
2
A0019142
If process temperatures are high, the device must be included in normal tank insulation to
prevent the electronics heating up as a result of heat radiation or convection. The
insulation may not exceed beyond the neck of the housing.
6.8
Turning the transmitter housing
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned:
max. 350°
8 mm
8 mm
A0013713
1. Unscrew the securing screw using an open-ended wrench.
2. Rotate the housing in the desired direction.
3. Tighten the securing screw (1,5 Nm for plastics housing; 2,5 Nm for aluminium or
stainless steel housing).
Summary of Contents for Micropilot FMR51
Page 197: ......
Page 198: ...www addresses endress com 71344019 71344019 ...