Micropilot FMR10
Diagnostics and troubleshooting
Hauser
27
9.3
Diagnostic event in the operating tool
If a diagnostic event is present in the device, the status signal appears in the top left status
area of the operating tool along with the corresponding symbol for the event level in
accordance with NAMUR NE 107:
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
Calling up remedial measures
‣
Navigate to the
Diagnostics
menu
In the
Actual diagnostics
parameter the diagnostic event is shown with event text
9.4
List of diagnostic events
Diagnostic
number
Short text
Remedy instructions
Status signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of electronic
270
Main electronic
failure
Exchange device
F
Alarm
271
Main electronic
failure
1. Restart device
2. If failure remains, exchange
device.
F
Alarm
272
Main electronic
failure
1. Restart device
2. Check enviroment for strong
EMC fields
3. If failure remains, exchange
device.
F
Alarm
283
Memory content
1. Transfer data or reset device
2. Contact service
F
Alarm
Diagnostic of configuration
410
Data transfer
1. Check connection
2. Retry data transfer
F
Alarm
411
Up-/download active
Up-/download active, please wait
C
Warning
435
Linearization
Check linearization table
F
Alarm
438
Dataset
1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M
Warning
441
Current output 1
1. Check process
2. Check current output settings
S
Warning
491
Current output 1
simulation
Deactivate simulation
C
Warning
585
Simulation distance
Deactivate simulation
C
Warning
586
Record map
Recording of mapping
please wait
C
Warning
Diagnostic of process
801
Energy too low
Increase supply voltage
S
Warning
825
Operating
temperature
1. Check ambient temperature
2. Check process temperature
S
Warning