Installation
25
3.2
Installation instructions
3.2.1
Mounting tool
To install in the control panel, all you need is a screwdriver.
3.2.2
Panel mounting, Installation dimensions
Fig. 2:
Panel mounting and installation dimensions. All dimensions in mm or (inch)
• Installation depth without terminal cover: approx. 158 mm (6.22") (incl. terminals and
fastening clips)
• Installation depth with terminal cover: approx. 197 mm (7,76")
• Panel cutout: 138
+1
x 138
+1
mm (5.43
+0.04
x 5.43
+0.04
")
• Panel thickness: 2 to 40 mm (0.08 to 1.58")
• Max. viewing angle range: from the display central axis 50° in all directions
• Securing to DIN 43 834
1. Push the unit through the panel cutout from the front. To avoid heat accumulation, we
recommend keeping a distance of > 15 mm (>0.59 inch) from the walls and other units.
2. Hold the unit horizontally and then hang the two jack screws into the openings (either
as shown in figure 3 the upper opening on the left and the lower opening on the right
side of the housing, or use the openings on top and bottom of the housing).
107.1 (4.22)
27
(1.06)
8.77
(0.3)
58
(0.28)
196 (7.72)
20
(0.79)
158 (6.22)
157.4 (6.20)
192.3 (7.57)
37.07
(1.46)
149.2
(5.87)
195.2
(7.69)
5
(0.2)
141 (5.55)
138
(5.43
)
+1
+0.04
138 (5.43)
138
(5.43)
Summary of Contents for Memograph M RSG40
Page 21: ......
Page 37: ...Commissioning and operation 37 ...
Page 39: ......
Page 57: ......
Page 74: ...Messa in servizio e funzionamento 74 ...
Page 75: ...Messa in servizio e funzionamento 75 ...
Page 76: ...www addresses endress com ...