Operation
Liquistation CSF28
36
Hauser
Function
Info
Display
Backlight
=
Automatic
The backlighting is switched off automatically after a short time if a button is not
pressed. It switches back on again as soon as you press the navigator button.
Backlight
=
On
The backlighting does not switch off automatically.
Device restart
Restart and keep all the settings
Factory default
Restart with factory settings; settings that are not saved are lost.
Firmware update
Current firmware version, installation using SD card.
Activation codes
Activation codes are required for:
Additional functionality
Change key lock password
To protect against unauthorized access
Communication settings
Webserver
Web server settings and manual assignment of the IP address
Settings for the sampling programs
Sampling
Device-specific settings for sampling that apply for all sampling programs and
manual samples.
10.2.2 Current and binary input for flowmeter
Assigning the current input or binary input
The inputs for a flowmeter are assigned using the Commissioning Wizard.
‣
In the
Guidance
menu, start the
Commissioning wizard
and follow the instructions.
The current input or binary input can now be selected in the
Commissioning
wizard
.
Configuring the current input or binary input
The following configuration options are available for the current input:
• Choice of 4 to 20mA or 0 to 20mA
• Selection of
Unit of flow
• Value for the end of the measuring range; 20 mA is assigned to this value
The following configuration options are available for the binary input:
• Choice of unit for the volume
• Pulse frequency; what volume does 1 pulse correspond to
The input is only visible in the menu if it was assigned in the Commissioning Wizard. The
configuration is primarily performed in the Commissioning Wizard but can also be
modified in the menu:
‣
In the
Application
/
Inputs
menu, set the input that is displayed to the desired values.
10.2.3 Sampling settings
Configuring general settings for sampling
A special wizard that guides you through the functions is available for the configuration of
a sampling program. A program can only be created with the Program Wizard. Certain
parameters can be changed via the menu:
•
Bottle distribution
(read only)
• Bottle volume
•
Dosing volume
(for vacuum pump)
Summary of Contents for Liquistation CSF28