Commissioning
Levelflex M FMP40 with HART/4...20 mA
50
Hauser
Function "Full Calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level (= span).
L00-FMP4xIxx-14-00-06-en-002
Function "Upper Block. Dist" (059)
For rod and rope probes with lengths of up to 8 m, the upper blocking distance is preset to 0.1 m
on delivery.
Blocking distances and measuring range depending on probe type
At the lower end of the probe, accurate measuring is not possible, see section "Maximum measured
error" on
!
Note!
Reliable measurement cannot be guaranteed within the blocking distance.
⇒
E HAUSER
E
+
–
100%
0%
F
DK
2
DK
1
F = full calibration (= span)
Fmax = E – upper blocking distance
⇒
E HAUSER
E
+
–
FMP40 (interface)
LN [m]
UB [m]
min
max
min
Coax probe
0,3
4
0
16 mm rod probe in the
bypass
0,3
4
0,1
1)
1)
The blocking distances indicated are preset. The upper blocking distance UB can be entered manually.
6 mm rod probe in the
bypass
0,3
2
0.1
)
Rope probe in free field
2)
2)
Measurements in free field available on request.
0,3
10
3)
3)
Larger measuring range available on request.
0.1
)
Summary of Contents for Levelflex M FMP40
Page 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Page 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Page 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Page 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Page 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...