Operating menu
Levelflex FMP56, FMP57 FOUNDATION Fieldbus
202
Hauser
Description of parameters
Navigation
Expert → Diagnostics → Simulation
Assign measurement variable
Navigation
Expert → Diagnostics → Simulation → Assign meas.var.
Description
Selct process variable to be simulated.
Selection
• Off
• Level
• Interface
• Level linearized
• Interface linearized
• Thickness linearized
Factory setting
Off
Additional information
• The value of the variable to be simulated is defined in the
Process variable value
• If
Assign measurement variable
≠
Off
, a simulation is active. This is indicated by a
diagnotic message of the
Function check (C)
category.
Process variable value
Navigation
Expert → Diagnostics → Simulation → Proc. var. value
Prerequisite
Assign measurement variable (→ 202)
Off
Description
Specify value of the process value being simulated.
User entry
Signed floating-point number
Factory setting
0
Additional information
Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Switch output simulation
Navigation
Expert → Diagnostics → Simulation → Switch sim.
Description
Switch the simulation of the switch output on or off.
*
Visibility depends on order options or device settings