iTHERM TrustSens TM371, TM372
Operating menu and parameter description
Hauser
99
Factory setting
•
Simulation value 1
: 4.00 mA, not activated
•
Simulation value 2
: 12.00 mA, not activated
•
Simulation value 3
: 20.00 mA, not activated
•
Low alarm
and
High alarm
not activated
Loop check interval
Navigation
Expert → Output → Loop check configuration → Loop check interval
Description
Displays the duration each single value is simulated.
User entry
4 to 255 s
Factory setting
4 s
14.4.3 "Communication" submenu
"HART configuration" submenu
Navigation
Setup → Device tag
Expert → Communication → HART configuration → Device tag
HART short tag
Navigation
Expert → Communication → HART configuration → HART short tag
Description
Use this function to define a short tag for the measuring point.
User entry
Up to 8 alphanumeric characters (letters, numbers and special characters).
Factory setting
8 x '?'
HART address
Navigation
Expert → Communication → HART configuration → HART address
Description
Use this function to define the HART address of the device.
User entry
0 ... 63