Operating menu and parameter description
iTHERM TrustSens TM371, TM372
78
Hauser
14.1 Setup menu
This menu contains all the parameters that are needed to configure the basic settings of
the device. The thermometer can be put into operation with this limited parameter set.
Device tag
Navigation
Setup → Device tag
Diagnostics → Device information → Device tag
Expert → Communication → HART configuration → Device tag
Description
Use this function to enter a unique name for the measuring point so it can be identified
quickly within the plant.
User entry
Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /)
Factory setting
Depends on the product root and the serial number
Unit
Navigation
Setup → Unit
Expert → System → Unit
Description
Use this function to select the engineering unit for all the measured values.
Options
• °C
• °F
• K
• °R
Factory setting
°C
Additional information
Please note that if the factory setting (°C) is switched to another unit, all the
temperature value settings will be converted to fit to the setted temperature unit.
Example: Upper range value is set to 150 °C. After the unit was switched to °F, the
new converted upper range value = 302 °F.
4 mA value
Navigation
Setup → Lower range value
Expert → Output → 4 mA value
Description
Use this function to assign a measured value to the current value 4 mA.
Factory setting
0 °C