iTHERM TrustSens TM371, TM372
Operating menu and parameter description
Hauser
97
User entry
3.5 to 4.25 mA
Factory setting
4 mA
Additional information
The trimming only affects current loop values from 3.8 to 20.5 mA. Failure mode with
Low Alarm
and
High Alarm
current values are not subjected to the trimming.
Current trimming 20 mA
Navigation
Expert → Output → Current trimming 20 mA
Description
Use this function to set the correction value for the current output at the end of the
measuring range at 20 mA.
User entry
19.50 to 20.5 mA
Factory setting
20.000 mA
Additional information
The trimming only affects current loop values from 3.8 to 20.5 mA. Failure mode with
Low Alarm
and
High Alarm
current values are not subjected to the trimming.
"Loop check configuration" submenu
Loop check configuration
Navigation
Expert → Output → Loop check configuration → Loop check configuration
Description
This function is active when there is at least one value defined. The loop check function
will run by each restart (power up) of the device. Measure the loop current with the
amperemeter. If the measured values deviates from the simulation values, these current
output values have to be adjusted.
To activate the loopcheck, define and activate at least one of the following values.