TMT84
Operation and commissioning
Hauser
37
5.3
Configuration of the head transmitter and PA functions
PROFIBUS
®
PA functions and device-specific parameters are configured via fieldbus
communication. The following configuration systems are available for this purpose:
• Hauser FieldCare (DTM)
• SIMATIC PDM (EDD)
!
Note!
A detailed step-by-step description of the procedure for commissioning the fieldbus functions,
together with information on configuring device-specific parameters, is given in the Operating
Instructions on the CD-ROM provided.
Device description files
PROFIBUS
®
PA protocol (IEC 61158-2, MBP):
5.4
Hardware settings (DIP switches)
DIP switches on the rear of the display are used to enable and disable hardware write protection,
configure the device address and to switch (turn) the display 180°. When write protection is
active, parameters cannot be modified.
The simulation mode via the hardware setting must be changed before the software setting.
Valid for firmware/software:
1.00.zz
1.01.zz
PROFIBUS
®
PA device data
Profile version:
3.01
3.02
TMT84 device ID:
Profile ID:
1551
hex
Depending on the profile GSD file used:
0x9703, 0x9702, 0x9701 or 0x9700
GSD information
TMT84 GSD:
Profile GSD:
Bitmaps:
Extended
PA139700.gsd
PA139701.gsd
PA139702.gsd
PA139703.gsd
EH1551_D.bmp/.dib
EH1551_N.bmp/.dib
EH1551_S.bmp/.dib
Compatibility matrix:
| EH3x1551.gsd | EH021551.gsd
1.00.zz | OK | STOP*
1.01.zz | OK | OK
*Can be used if the "C1_Read_Write_supp = 1" entry in the
GSD is set to "C1_Read_Write_supp = 0".
Operating program/device driver: Source for device descriptions/program updates, free downloads on Internet:
GSD
• www.endress.com (
→
Download
→
Software
→
Device Drivers)
• www.profibus.com
FieldCare/DTM
• www.endress.com (
→
Download
→
Software
→
Device Drivers)
SIMATIC PDM
• www.endress.com (
→
Download
→
Software
→
Device Drivers)
• www.fielddevices.com