Operating instructions

iTEMP

® 

 HART

®  

 TMT182

Temperature head transmitter

6

Summary of Contents for iTEMP TMT182

Page 1: ...BA105R 24 ae 04 05 51006279 Operating instructions iTEMP HART TMT182 Temperature head transmitter 6...

Page 2: ...TMT182 2 Endress Hauser...

Page 3: ...2 COMMUWIN II operating program 15 6 Commissioning 16 6 1 Installation and function check 16 6 2 Commissioning 16 6 2 1 Quick Setup 16 6 2 2 Configuration with HART protocol and DXR275 DXR375 hand op...

Page 4: ...ight to change and or improve the product design and specifications without notice Warning Failure to follow these installation guidelines could result in death or serious injury Make sure only qualif...

Page 5: ...the unit functions A complete description of all the functions as well as a detailed overview of the function matrix can be found in this chapter Quick Setup Fast entry into the unit configuration fo...

Page 6: ...nt operator must make sure that the measurement system has been correctly wired to the connection schematics Electrical temperature sensors such as RTD s and thermocouples produce low level signals pr...

Page 7: ...a without prior notice Your E H distri butor can supply you with current information and updates to these Operating Instructions 1 4 Returns Returns Please follow the Return Authorization Policy which...

Page 8: ...ormity 4 The devices are designed to meet state of the art safety requirements have been tested and left the factory in a condition in which they are safe to operate The devices comply with the applic...

Page 9: ...MT182 Installation screws installation springs and E ring Operating instructions Control drawing for use in hazardous areas Note Please take note of the head transmitter accessories in chapter 8 Acces...

Page 10: ...the connection head in such a way so that the current output terminals terminal 1 and 2 are towards the cable entry gland Pos 7 Fix the head transmitter Pos 4 and sensor inset Pos 5 into the connectio...

Page 11: ...ly Pos 5 into the the transmitter housing Pos 4 using a screwdriver Feed the sensor inset cables through the conduit of the transmitter housing and the central hole in the head transmitter Attach the...

Page 12: ...ollowed parts of the electronic circuit will be damaged 4 2 1 Sensors Connect the sensor cables to the respective head transmitter terminals Terminals 3 to 6 by follo wing the wiring diagram see fig 6...

Page 13: ...and see fig 8 Connection of a HART hand operated module DXR275 DXR375 ig 7 Electrical connection of the HART operated module a HART module a HART module connected to the communication sockets of a pow...

Page 14: ...signal appears noisy or erratic grounding the current signal loop at a single point may solve the problem The best place to ground the loop is at the negative terminal of the power supply Do not groun...

Page 15: ...m for remote operation of field and panel mounted instrumen tation Application of the Commuwin II operating program is possible independent of the type of unit and communication mode HART or PROFIBUS...

Page 16: ...XPANDED Windows 2000 and Windows XP classic category view Select Expanded settings for COM1 using the menu START SETTINGS SYSTEM CON TROL SYSTEM HARDWARE DEVICE MANAGER CONNECTIONS COM and LPT COMMUNI...

Page 17: ...er This matrix systematically contains all HART accessible functions 2 Using Matrix Parameter the function group can be selected e g basic calibration and then followed by the required function e g Se...

Page 18: ...anual BA 124F 00 en Commuwin II operating program More details see www us endress com Descriptor 2 Note are marking the Quick Setup menu The black highlighted function fields Int temperature Filter ti...

Page 19: ...rable parameters Unit function description see Description of unit functions on page 20 Standard settings Type of sensor Connection mode 2 3 or 4 wire connection on RTD Units C F or K Measurement rang...

Page 20: ...t The HART operating module DXR275 DXR375 display is indicated by the following symbol 7 Function group WORKING PARAMETERS Primary value V0H0 7 PV Display of actual measured temperature Display 7 digi...

Page 21: ...C 58 F 1768 C 3214 F Type T 270 C 454 F 400 C 752 F Type U 200 C 328 F 600 C 1112 F Polynom TC 270 C 454 F 2500 C 4532 F Pt100 DIN Temp Compensation V2H1 Selection of temperature compensation of the...

Page 22: ...polynome TC 1 Coefficient X0 V3H0 Input of first coefficient for customer specific linearization polynome 4th grade with five coefficients see chapter 6 2 4 Coefficient X1 V3H1 Input COEFFICIENT X1 se...

Page 23: ...imulation mode Entry Off On Off Current out sim V9H8 Entry of simulation value current Entry 3 58 to 21 7 mA Security locking V9H9 Release code for setting up Entry Lock 0 Release 281 281 Function gro...

Page 24: ...y variable output information r 16 Read final assembly number r 17 Write message w 18 Write tag descriptor date w 19 Write final assembly number w Common practice 34 Write primary variable damping val...

Page 25: ...following address www readwin2000 com Please contact your supplier when ordering e g spare parts When ordering accessories or spare parts please state the serial number of the unit 9 Trouble shooting...

Page 26: ...e head transmitter Replace head transmitter Fault Cause Action cure Fault current 3 6 mA or 21 mA Defective sensor Check sensor Incorrect RTD connection Reconnect cables correctly connec tion diagram...

Page 27: ...Sensor incorrectly connected Connect sensor correctly to terminal plan polarity Defective sensor Replace sensor Programming Sensor type RTD setup set up cor rect thermocouple Incorrect 2 wire connect...

Page 28: ...riable Temperature temperature linear transmission behavior resistance and voltage Measuring range The transmitter monitors different measuring ranges depending on the sensor connection and input sign...

Page 29: ...nced Diagnostics version see Product structure If corrosion detection is active the response time is 2 s Resistance transmitter Resistance 10 to 400 10 to 2000 10 100 Thermocouples TC to NIST Monograp...

Page 30: ...10 4 Power supply Electrical connection See Overview on page 12 Supply voltage Ub 11 5 to 35 V polarity protected For hazardous location please see control drawing Warning The unit must only be powere...

Page 31: ...ll scale value Long term stability 0 18 F year 0 1 C year or 0 05 year Values under reference operating conditions refer to the set span The highest value is valid Influence of cold junction Pt100 IEC...

Page 32: ...r IEC 61326 Amendment 1 1998 and NAMUR NE 21 This recommendation is a uniform and practical way of determining whether the devices used in laboratory and process control are immune to interference wit...

Page 33: ...ction compensation of wire resistance with 2 wire connection failure mode output signal 4 to 20 20 to 4 mA digital filter damping offset TAG descriptor 8 16 characters output simulation customer speci...

Page 34: ...ne approval 8 H HART function matrix 18 HART hand operating module DXR 275 13 HART protocol 14 Hazardous areas 7 Head transmitter 9 I Installation angle 9 Installation point 9 Installation screws 9 in...

Page 35: ...TMT182 Endress Hauser 35...

Page 36: ...37 inquiry us endress com www us endress com M xico Endress Hauser M xico S A de C V Av Gustavo Baz No 43 Fracc Bosques de Echegaray Naucalpan de Ju rez C P 53310 Estado de M xico M xico Tel 52 55 537...