Installation instructions

TMT125

30

Hauser

a0006835

Fig. 3:  Fieldhousing mounting

A

:

 Mounting holes for fixing with screws M6

B

:

 Earthing point

3.4

Mounting of the DIN rail transmitter

The DIN rail transmitter is designed for mounting on a 35 mm DIN rail in accordance with IEC 
60715 and must be protected against electrostatic discharge.

The device must be mounted inside a housing that corresponds to at least degree of protection:
• IP 20 in accordance with IEC 60529 or higher for category 2G (Zone 1) application. The 

housing must be suitable for this application.

• IP 54 in accordance with IEC 60529 or higher for category 3G (Zone 2) application. The 

housing must be suitable for this application.

"

Caution! 
Plastic housing must be designed in accordance with IEC 60079-0 or need to be protected 
against electrostatic discharge.

Now snap the device onto the DIN rail by firstly hanging the device on the DIN rail and then 
pressing it down gently until it engages (

å

4, item 1 and 2).

Summary of Contents for iTEMP TMT125

Page 1: ...H1 87484 Nesselwang Made in Germany 2006 0032 0123456789101 1019876543210 TMT125 XXXXXXXX Ser No TAG No Order Code TMT125 PTB 05 ATEX xxxxX II 3G EEx nA II T4 II 3G EEx nL IIC T4 II 3 G EEx nL IIC T4...

Page 2: ......

Page 3: ...e 9 3 1 Warenannahme Transport Lagerung 9 3 2 Montagebedingungen 9 3 3 Montage Feldgeh use 9 3 4 Einbau des f r Hutschienen ausgelegten Transmitters 10 3 5 Montagekontrolle 11 4 Verdrahtung 12 4 1 Ver...

Page 4: ...n Widerstandsthermometern RTD und Thermoele menten sowie Widerstands und Millivolt Signale ber FOUNDATION Fieldbus Es emp fiehlt sich jeden Kanal individuell zu konfigurieren Das Ger t kann auch mit d...

Page 5: ...erte und Sicherheitshinweise m ssen konse quent beachtet werden Das Ger t kann in Ex Bereichen der Kategorie 2G Zone 1 oder Kategorie 3G Zone 2 instal liert werden Bei Anwendungen der Kategorie 2G Zon...

Page 6: ...Ger tes f hren k nnen Achtung Dieses Symbol deutet auf Aktivit ten oder Vorg nge hin die wenn sie nicht ordnungsgem durchgef hrt werden zu fehlerhaftem Betrieb oder zur Zerst rung des Ger tes f hren...

Page 7: ...am Ger t mit dem auf dem Liefer schein a0006759 Abb 1 Typenschild des Temperaturtransmitters Beispiel f r ein an einer Hutschiene installiertes Ger t a0006758 Abb 2 Typenschild auf dem Feldgeh use Bei...

Page 8: ...heitsbestimmungen f r elektrische Mess Steuer Regel und Laborger te Das in dieser Betriebsanleitung beschriebene Ger t erf llt somit die gesetzlichen Anforderungen der EU Richtlinien Der Hersteller b...

Page 9: ...beide Ausf hrungen 40 bis 70 C 40 bis 158 F Relative Luftfeuchtigkeit 95 nicht kondensierend gilt f r Hutschienenversion Klimaklasse entspricht den Anforderungen der Klasse C1 C3 gem IEC 60721 4 3 Hi...

Page 10: ...terzubringen das mindestens folgende Schutzart erf llt IP 20 gem IEC 60529 oder h her f r Anwendungen der Kategorie 2G Zone 1 Das Geh use muss f r diese Anwendung geeignet sein IP 54 gem IEC 60529 ode...

Page 11: ...rolle F hren Sie nach der Montage des Ger tes folgende Kontrollen durch Ger tezustand und spezifikationen Hinweise Entspricht das Ger t den Messstellenspezifikationen wie Umgebungs temperatur Montageo...

Page 12: ...ektronik f hren Hinweis Bei der Installation von eigensicheren Feldbus Segmenten ist die EN 60079 14 IEC 60079 14 zu beachten In der Bundesrepublik Deutschland muss dar ber hinaus auch das National Fo...

Page 13: ...t EEx ia IIC IIB bzw EEx ib IIC IIB mit folgenden Werten Hinweis ber die Serviceschnittstelle durchzuf hrende Parametrieraufgaben d rfen ausschlie lich von Endress Hauser Servicemitarbeitern durchgef...

Page 14: ...nden Kabelschelle Die Montagebedingungen 9 sind einzuhalten Nicht verwendete Kabelverschraubungen m ssen mit einem entsprechenden Blindstopfen ver schlossen oder durch einen geeigneten Schraubverschlu...

Page 15: ...ben Inneres Kunststoffelement ausreichend weit ber das Kabel schieben sodass die Ummantelung vollst ndig umgeben ist Ummantelung darf nicht ber das Ende des inneren Kunststoffelementes hinausragen 4 A...

Page 16: ...dbuskabels darf nicht unterbrochen werden Der Anschluss der Abschirmung muss immer so kurz wie m glich gehalten werden T09 TMT125FF 04 xx xx xx 001 Abb 7 Ger testecker f r den Anschluss an den FOUNDAT...

Page 17: ...Geh useschrauben und Schraubdeckel m ssen fest angezogen sein Die f r den Anschluss verwendeten Kabel m ssen den spezifizierten Au endurchmesser auf weisen z B M20 x 1 5 Kabeldurchmesser 8 bis 12 mm K...

Page 18: ...el von Zug entlastet Sind Hilfsenergie Feldbuskabel korrekt angeschlossen 12 Sind alle Anschlussklemmen fest angezogen Sind alle Kabelverschraubungen montiert fest angezogen und dicht Kabelf hrung mit...

Page 19: ...nalisiert Netz ein 2 Rote LED leuchtet kontinuierlich oder blinkt Signalisiert Kommunikationsstatus Hardware oder Kommunikationsfeh ler 3 rot blinkende LEDs Signalisiert Status des angeschlossenen Sen...

Page 20: ...ist ein einheitlicher Zugriff auf alle Netz werk und Feldbusger tedaten m glich Systemdateien F r die Inbetriebnahme und die Netzwerkprojektierung ben tigen Sie folgende Dateien Inbetriebnahme Ger te...

Page 21: ...n wird dringend empfohlen den Schalter im Normal betrieb auf AUS zu stellen Schalter 2 Hardware Schreibschutz EIN AUS Ist der Schreibschutz aktiviert Einstellung EIN kann das Ger t nicht l nger ber de...

Page 22: ...Stromversorgung angeschlossen ist f hrt das Ger t hoch und die LEDs zeigen eine Art Fortschrittsbalken Anschlie end leuchtet die gr ne LED und signalisiert damit Netz ein w hrend die LEDs f r eventue...

Page 23: ...ions 29 3 1 Incoming acceptance transport storage 29 3 2 Mounting conditions 29 3 3 Fieldhousing mounting 29 3 4 Mounting of the DIN rail transmitter 30 3 5 Post mounting check 31 4 Wiring 32 4 1 Quic...

Page 24: ...measuring sensors RTD s thermocouples TC s resistance and millivolt signals via FOUNDATION Fieldbus Each channel could be configured independently The device can be used for FOUNDATION Fieldbus H1 bu...

Page 25: ...number of this document XA is also indicated on the nameplate The device may be installed in category 2G Zone 1 or category 3G Zone 2 of a hazardous area For category 2G Zone 1 applications the type...

Page 26: ...if not carried out properly Caution This symbol draws attention to activities or procedures that can lead to defective operation or to destruction of the unit if not carried out properly Note This sym...

Page 27: ...e DIN rail or field housing device with the delivery note a0006759 Fig 1 Nameplate of the temperature transmitters DIN rail device as example a0006758 Fig 2 Nameplate on the field housing example 1 Or...

Page 28: ...C 61 010 Safety Requirements for Electrical Equipment for Measurement Control and Laboratory Use The device described in these Operating Instructions is therefore in conformity with the statutory requ...

Page 29: ...6 x 140 mm 5 51 x 84 mm 3 31 BxHxD 3 2 2 Mounting point Ambient temperature both versions 40 to 70 C 40 to 158 F Relative humidity 95 not condensing valid for the DIN rail version Climate class meets...

Page 30: ...that corresponds to at least degree of protection IP 20 in accordance with IEC 60529 or higher for category 2G Zone 1 application The housing must be suitable for this application IP 54 in accordance...

Page 31: ...60715 3 5 Post mounting check After mounting the device always run the following final checks Device condition and specifications Notes Has the device been mounted in accordance with specifications Ch...

Page 32: ...ction of parts of the electronics Note When installing intrinsically safe fieldbus segments EN 60079 14 IEC 60079 14 must be observed For the Federal Republic of Germany the National Foreword of DIN E...

Page 33: ...Tasks for parameterization via the service interface must only be performed by E H service only 4 2 Connecting the device 4 2 1 Cable glands or entries If the device has not been grounded as a result...

Page 34: ...9 must be observed Cable glands that are not in use must be closed off with a corresponding stop plug or replaced by an appropriate screw plug The required degree of protection IP 67 must be observed...

Page 35: ...nside plastic part far enough over the cable that the covering is completely surrounded The covering must not stand out over the end of the inside plastic part 4 Pull the shield over the inside plasti...

Page 36: ...intact The shielding connection must always be kept as short as possible T09 TMT125FF 04 xx xx xx 001 Fig 7 Connectors for connecting to the FOUNDATION Fieldbus A Fieldbus connector pin assignment co...

Page 37: ...oves The seals must be dried cleaned or replaced if necessary All housing screws and screw caps must be firmly tightened The cables used for connection must be of the correct specified outside diamete...

Page 38: ...he power supply and fieldbus cables correctly connected 32 Are all terminals firmly tightened Are all the cable glands installed tightened and sealed Cable run with water trap 33 und 37 Are all the ho...

Page 39: ...on Description 1 Green lit LED Signalizes Power on 2 Red lit or flashing LED Signalizes communication status hardware or communication error 3 Red flashing LEDs Signalizes connected sensor status sens...

Page 40: ...cess to all the network and fieldbus device data System files You require the following files for commissioning and configuring the network Commissioning DD Device Description sym ffo files Network co...

Page 41: ...sons is strongly recommended to set the switch to OFF for normal operation Switch 2 Hardware write protection ON OFF Parameterization of the device via the bus is no longer possible when write protect...

Page 42: ...t Connect the fieldbus to appropriate terminals on the device 32 If a power supply is connected the device boots up and the LEDs show a kind of progress bar In the following the green power LED is on...

Page 43: ...TMT125 Endress Hauser 43...

Page 44: ...www endress com worldwide KA241R 09 a2 10 06 71034583 FM SGML6 0 ProMoDo...

Reviews: