Installation instructions
TMT125
30
Hauser
a0006835
Fig. 3: Fieldhousing mounting
A
:
Mounting holes for fixing with screws M6
B
:
Earthing point
3.4
Mounting of the DIN rail transmitter
The DIN rail transmitter is designed for mounting on a 35 mm DIN rail in accordance with IEC
60715 and must be protected against electrostatic discharge.
The device must be mounted inside a housing that corresponds to at least degree of protection:
• IP 20 in accordance with IEC 60529 or higher for category 2G (Zone 1) application. The
housing must be suitable for this application.
• IP 54 in accordance with IEC 60529 or higher for category 3G (Zone 2) application. The
housing must be suitable for this application.
"
Caution!
Plastic housing must be designed in accordance with IEC 60079-0 or need to be protected
against electrostatic discharge.
Now snap the device onto the DIN rail by firstly hanging the device on the DIN rail and then
pressing it down gently until it engages (