Installation
Proline Promass 80
24
Hauser
3.3.3
Turning the local display
1.
Unscrew cover of the electronics compartment from the transmitter housing.
2.
Press the side latches on the display module and remove the module from the electronics
compartment cover plate.
3.
Rotate the display to the desired position (max. 4 × 45 ° in both directions), and reset it onto
the electronics compartment cover plate.
4.
Screw the cover of the electronics compartment firmly back onto the transmitter housing.
a0003236
Fig. 18:
Turning the local display (field housing)
3.4
Post installation check
Perform the following checks after installing the measuring device in the pipe:
4 x 45°
Device condition and specifications
Notes
Is the device damaged (visual inspection)?
-
Does the device correspond to specifications at the measuring point, including
process temperature and pressure, ambient temperature, measuring range etc.?
Installation
Notes
Does the arrow on the sensor nameplate match the direction of flow through the
pipe?
-
Are the measuring point number and labeling correct (visual inspection)?
-
Has the correct orientation been chosen for the sensor, in other words is it suitable
for sensor type, fluid properties (outgassing, with entrained solids) and fluid
temperature?
Process environment / process conditions
Notes
Is the measuring device protected against moisture and direct sunlight?
-