Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Commissioning
Hauser
39
4. Setup → Max. filling speed solid
By selecting the maximum expected filling and draining speed the signal evaluation
is automatically optimized for the process. Note: The filling and draining speeds can
be set separately as the filling and draining procedures may be different. Note:
With the ‘No filter / test’ option all signal evaluation filters are deactivated. This
option should exclusively be used for tests.
5. Setup → Max. draining speed solid
By selecting the maximum expected filling and draining speed the signal evaluation
is automatically optimized for the process. Note: The filling and draining speeds can
be set separately as the filling and draining procedures may be different. Note:
With the ‘No filter / test’ option all signal evaluation filters are deactivated. This
option should exclusively be used for tests.
6. Setup → Empty calibration
Specify empty distance E (distance from reference point R to 0% mark).Setup
→ Advanced setup → Level → Tank/silo heightIf the parametrized measuring range
(Empty calibration) differs significantly from the tank or silo height, it is
recommended to enter the tank or silo height in this parameter. Example:
Continuous level monitoring in the upper third of a tank or silo. Note: For tanks
with conical outlet, this parameter should not be changed as in this type of
applications 'Empty calibration' is usually not << the tank or silo height.
7. Setup → Full calibration
Distance between minimum level (0%) and maximum level (100%).
8. Setup → Level
Currently measured level
9. Setup → Distance
Distance between lower edge of flange or thread and medium surface.
10. Setup → Signal quality
Displays the signal quality of the analyzed level echo.
11. Setup → Mapping → Confirm distance
Compare the distance displayed with the actual value to start recording an
interference echo map.
12. Setup → Advanced setup → Level → Level unit
Select the level unit: %, m, mm, ft, in (factory setting: %)
It is strongly recommended to adjust the maximum filling and draining speed to the
actual process.
9.7
User-specific applications
To configure the parameters for user-specific applications, see:
BA01123F - Operating Instructions, FMR56/FMR57, FOUNDATION Fieldbus