Operation
EngyCal RS33
32
Hauser
6
Operation
6.1
General notes for operation
The steam calculator can be configured using keys or using the "FieldCare" operating software.
Die Bediensoftware inklusive Schnittstellenkabel ist als Bestelloption erhältlich, d.h. nicht
Grundbestandteil des Lieferumfangs.
The configuration is locked if the device is locked by the hardware lock (→ 33), user code
or digital input.
Details, see section "Access protection" in the Operating Instructions.
6.2
Display and operating elements
1
2
3
5
4
A0013444
24
Display and operating elements of the device
1
LED green, "Operation"
2
LED red, "Fault indicator"
3
USB connection for configuration
4
Operating keys: -, +, E
5
160x80 DOT matrix display
Green LED for voltage, red LED for alarm/error. Green LED is always illuminated as soon
as power is supplied to the device.
Slow flashing of the red LED (approx. 0.5 Hz): the device has been put into bootloader
mode.
Fast flashing of the red LED (approx. 2 Hz): in normal operation: maintenance required.
During firmware update: data transmission active.
Red LED illuminated constantly: device error.