background image

Technical data

79

Rear illumination:

50,000 h half value time (= half brightness)

Number of colors:

64 colors

Point of view:

Maximum point of view range: From the display center 50° to the left and right, 20° upward, 30° 
downward.

Display modes:

Curves/load curves, curves in ranges, digital display, bar graph, events list (set points/power 
failure), status display, history display in curve form with display of digital measured values, date 
and time

10.8.2

Operating elements

Keyboard:

Option of operation and configuration via 7 push buttons on the front side in interactive dialog with 
the screen or using the provided PC software. Display of integrated operating instructions at the 
push of a button.

10.8.3

Data storage

Save cycle:

• Selectable save cycle: 1s / 2s / 3s / 4s / 5s / 10s / 15s / 20s / 30s / 1min / 2min / 3min / 

4min / 5min / 10min / 30min / 1h

Selected save cycle

Equal to a feed rate in 
mm/h

Equal to a feed rate in 
inch/h

1s

1000

40

2s

600

24

3s

300

12

4s

240

10

10s

120

4.8

20s

60

2.4

30s

30

1.2

1min (60s)

20

0.8

2min (120s)

10

0.4

4min (240s)

5

0.2

Summary of Contents for Ecograph T RSG30

Page 1: ...BA194R 09 en 13 10 No 51009564 Software ETU00xA V2 02 xx Operating Instructions Multi Channel Recorder RSG30 Ecograph T ...

Page 2: ...he unit Anything that is not described directly at the unit by plain text or menus is explained here Fig 1 Variable softkey e g calling up internal Help function in the Setup menu Index A very extensive index can be found at the end of these Operating Instructions It acts as a complement to the table of contents and helps you find special terms and functions 1 Consider the safety instructions Page...

Page 3: ...3 ...

Page 4: ...sages 22 5 6 Communication PC software installation 22 6 Commissioning 26 6 1 Function check 26 6 2 Switching on the unit 26 6 3 Unit Set up 26 6 4 The set up window at main menu 30 6 5 The main menu 54 6 6 Saving measured values 61 6 7 Important functions of the provided PC software 62 7 Maintenance 64 7 1 Software update via the provided PC software 64 7 2 Instruction for releasing a software op...

Page 5: ...ening and repairing electrical units 1 3 Operational safety The unit is safely built and tested according to state of the art technology and has left the factory in perfect condition as regards technical safety The applicable regulations and European standards have been taken into account Please observe the technical data on the nameplate The nameplate is on the left hand side of the housing Desk ...

Page 6: ...ied out properly Caution This symbol draws attention to activities or procedures that can lead to defective operation or to destruction of the unit if not carried out properly Note This symbol draws attention to activities or procedures that have an indirect effect on operation or can trigger an unforeseen unit reaction if not carried out properly ESD Electrostatic discharge Protect the terminals ...

Page 7: ...ption 6 Ambient temperature range 7 Unit approvals 2 2 Scope of delivery Unit with terminals as per your order 4 fastening clips USB cable Optional CompactFlash CF card CF card is enclosed separately PC operating and configuration software on CD ROM Delivery note Multilanguage Brief Operating Instructions as hard copy Operating Instructions on CD ROM locking plate Anything missing Then please info...

Page 8: ...e original packaging offers the best protection for this The permitted storage temperature is 20 to 60 C 4 to 140 F 3 2 Installation conditions Working temperature range 0 to 50 C 32 to 122 F max 75 rel humidity without condensation Caution To avoid heat accumulation please always ensure that the unit is sufficiently cooled Maintain distance from strong magnetic fields see Section 10 Technical dat...

Page 9: ...cumulation we recommend keeping a distance of 15 mm 0 59 in from the walls and other units 2 Hold the unit level and then hang jack screws in the openings 2 x top 2 x bottom 3 Tighten the screws on the jack screws equally with a screwdriver such that a secure seal to the control panel is guaranteed Note A distance of min 15 mm 0 59 in between the units has to be observed if aligning the units in t...

Page 10: ...late into the slit below the handle of the cover plate see Fig 4 Now you can lead seal or seal the cover plate with a suitable lock Fig 4 Inserting the locking plate 3 5 Post installation check After installing the control panel please check the following points Is the unit fixed firmly in the center of the control panel cutout Does the seal run all around the housing collar ...

Page 11: ... switch or circuit breaker when installing in a building This switch must be installed near to the unit easily accessible and be labeled as a separator An overcurrent protective unit nominal current 10 A is required for the power cable Note Please also refer to the terminal diagram on the rear of the unit 4 1 1 Channel color table When wiring the analog channels please ensure that the color displa...

Page 12: ...Wiring 12 4 1 2 Wiring diagram Fig 5 Circuit diagram ...

Page 13: ...hernet RS232 Rel2 41 42 31 32 21 22 11 13 12 L N PE Rel4 Rel3 Rel1 RS485 CH 4 CH 5 CH 6 611 612 613 614 615 616 411 412 413 414 415 416 CH 1 CH 2 CH 3 111 112 113 114 115 116 211 212 213 214 215 216 311 312 313 314 315 316 511 512 513 514 515 516 _ Y Y _ Out max 250 mA On connecting channels 1 4 see terminal connections CH 5 6 Sensor 1 e g TR10 from E H Sensor 2 External display optional e g RIA26...

Page 14: ...ted screwdriver size 0 Please note the following when connecting Digital I O wire cross section RS485 and analog inputs max 1 5 mm2 14 AWG spring terminals Power wire cross section max 2 5 mm2 13 AWG screw terminals Relay wire cross section max 2 5 mm2 13 AWG spring terminals Stripping length 10 mm 0 39 in Note No ferrules have to be used when connecting flexible wires to spring terminals 5 6 9 1 ...

Page 15: ...pe Terminal 100 230 VAC L N GND Phase L Zero conductor N Ground 24 V AC DC L N GND Phase L or Zero conductor N or Ground Type Terminal x11 x12 x13 x14 x15 x16 Current Voltage 1 V Voltage 1 V Resistance thermometer RTD 2 wire A B Resistance thermometer RTD 3 wire A b sense B Resistance thermometer RTD 4 wire A a sense b sense B Thermocouples TC L N PE CH x x11 x12 x13 x14 x15 x16 ...

Page 16: ... Auxiliary voltage output not stabilized max 250 mA Ground Approx 24 V DI3 93 92 91 Type Terminal 41 42 31 32 21 22 11 13 12 Alarm relay 1 Normally open contact NO 2 Changeover contact Normally closed contact NC 1 Relay 2 Switching contact Normally open contact NO 2 Relay 3 Switching contact Normally open contact NO 2 Relay 4 Switching contact Normally open contact NO 2 1 NC normally closed breake...

Page 17: ... is supported Fig 8 RJ45 socket assignment AT T256 LED description Beneath the Ethernet connection see rear of unit there are two light emitting diodes which indicate the status of the Ethernet interface Yellow LED link signal is on when the unit is connected to a network If this LED is not illuminated then communication is impossible Green LED Tx Rx when the unit is receiving or sending data it f...

Page 18: ...it meets all the requirements of ingress protection IP54 4 4 Post connection check After completing the unit s electrical connections carry out the following checks Pin of the SUB D9 socket 1 2 3 4 5 6 7 8 9 RS232 assignmen t Shield TxD data output RxD data input GND Fig 9 RS232 assignment Caution Unoccupied connections should be left empty The RS232 RS485 interfaces cannot be used simultaneously ...

Page 19: ...ting instructions Your unit displays instructions at the push of a button directly on screen This description is a supplement to the Operating Instructions built into the unit Anything that is not described directly in plain text or menus is explained here We reserve the right to make alterations that contribute to technical progress Fig 10 Variable softkey e g calling up internal Help function in...

Page 20: ...ds recording history display remove paper At Setup menu Moves the cursor bar upwards changes parameter signs W At display mode Forwards recording to current time wind on paper At Setup menu Moves the cursor bar downwards changes parameter signs F At display mode Displays main menu At Setup menu ENTER key Selection of the marked function start the parameter change Variable softkey e g calling up in...

Page 21: ...red value acquisition continues to run without interruption 4 At display mode Displays the current date time At Setup menu Displays the operating item 5 At display mode Indicates what portion of the CF card is already written to in At Setup menu Displays the operating code 6 At display mode Functions of the LED displays on the display as per NAMUR NE44 Green LED lights up power supply OK unit work...

Page 22: ...er Start Programs 5 6 2 Communication via USB USB driver installation Once the provided PC operating software has been installed successfully the unit can be connected to the PC with a USB cable The operating system automatically recognizes the new USB unit Note Proceed as follows to then install the USB driver depends on operating system 1 The Windows prompt Should a connection be established wit...

Page 23: ...m for unit The modem is therefore connected to the PC with its original cable 1 1 modem calble normally enclosed with every modem Initialization must be carried out with the same data format baudrate data bits parity with which the measuring unit works After successful initialization the modem is connected to the unit with a special modem cable Only three cables TxD RxD GND and 2 bridges on modem ...

Page 24: ...P address Subnetmask and Gateway are input directly at the unit Changes to the system parameters are not activated until the SETUP menu is closed and the settings accepted Only then will the unit work with the new settings Note It is not possible for several clients PC to communicate with a server unit at the same time If a second client PC tries to establish a connection he receives an error mess...

Page 25: ... 2 A new unit now has to be registered in the database After the unit description has been input select how the unit settings are to be transferred In this case select Ethernet TCP IP Fig 15 Registering a new unit in the PC database Now enter the IP address The port address is 8000 The unit address set at the unit and the release code must also be set correctly here Fig 16 Entering the IP address ...

Page 26: ... language The default setting for the operating language is English GB A different operating language can be configured in the set up see Section 6 4 1 F Set up Basic settings Language Fig 17 Change the operating language 6 3 Unit Set up 6 3 1 General Access to the set up is released when the unit leaves the factory and can be locked in various ways e g entering a 4 digit release code Chap 6 4 1 B...

Page 27: ... Delete internal memory 6 3 2 Set up via interface and provided PC software Fig 18 Example Set up via the provided PC software Procedure for set up via interface and the provided PC software Start Install the provided PC software on the PC or laptop see chapter 5 5 Connect the unit interface RS232 RS485 USB or Ethernet to the PC Check selected communication settings in the unit see Section 6 4 4 c...

Page 28: ...base and or register in the PC database at first In addition a CompactFlash card slot must be present at the PC Procedure set up via CompactFlash card 1 Copy set up to CompactFlash card Insert a formatted CompactFlash card into the unit In the main menu select CompactFlash CF functions Copy set up to CF In the main menu select CompactFlash CF functions Safely remove CF Remove the CompactFlash card...

Page 29: ...or return to previous screen UT Moves cursor left or right VW Moves bar up or down changes parameter sign F Enter key selects the highlighted function starts parameter change Note Every parameter is modified via a dialog box The altered settings only take effect once you return to normal operation by pressing Z several times confirm you accept changes with F Until this time the unit still works wi...

Page 30: ...2 Settings of the connected analog inputs incl set point settings relays and the digital input Signal analysis see Section 6 4 3 Set up in order to obtain signal analysis for presettable time ranges cycles as well as a manual reset of the signal analysis Function only visible if a digital input has been activated as a counter Communication see Section 6 4 4 Set up only required if you are using th...

Page 31: ...ion by pressing Z several times and confirming with F Until this time the unit still works with the previous data 6 4 1 Set up Basic settings Settings that are not channel specific this means date time etc Procedure for basic settings Start Assign unit identifier Select the operating language from the list Select decimal separator comma or point Select temperature unit C F K Select the save cycle ...

Page 32: ... length changes Tables to the typical recording length you will find in the technical data chapter 10 8 3 Alarm cycle Selects the cycle for alarm condition e g alarm set point violation in which data is stored and displayed Picklist off 1s to 1h 1min Release code Using this code set up access can be protected from unauthorized persons In order to change any parameter the correct code must be enter...

Page 33: ...wing addresses Off no changeover times required NT ST region only at NT ST changeover automatic Selects the regional settings for summer normal time changeover Picklist Europe USA Date NT ST only at NT ST changeover manual Day when in the spring a change from normal to summer time occurs Time NT ST only at NT ST changeover manual Time when the time is moved forward by 1 hour on the day of the chan...

Page 34: ...fier Group identifier Group identifier which is used by the provided PC software A 10 digit text can be entered here Factory setting Group 1 Grid divisions Indicates the number of lines amplitude grid that should be displayed on the screen in the display mode Curve Example display of 0 100 select 10 divisions display 0 14pH select 14 divisions Picklist 1 to 20 10 Fig 24 Grid divisions setting exam...

Page 35: ...a is deleted so that new data can be stored first in first out FIFO Option only possible for Protected format Separator for CSV only at Open format csv Specify which separator is used by your application e g in Excel semicolon Picklist comma semicolon Operating time only at Open format csv Specify the format for which operating times should be saved displayed 0000 00 00 Date time only at Open form...

Page 36: ...lways switched on Switch on for x min display goes dark after x minutes All other functions remain in operation Press an operating key Illumination is switched back on x 10 30 60 min Switched daily enter time span With this setting the display turns dark 1 minute after the last key was pressed ON daily from only at Switched daily Set time hh mm from which the rear illumination is to be switched of...

Page 37: ...ge for analog input e g 0 20 mA for current Enter channel identifier Select plot type Enter unit dimension Enter number of digits after decimal point Enter measuring range and zoom range Enter damping filter if necessary Enter offset for start and end of measuring range Set fault mode e g in event of cable open circuit Do set points have to be defined Yes See Signal Settings Set Points see Page 46...

Page 38: ...n analog signal Here the user can specify whether an analog signal is attached or whether a calculation should be performed Mathematics channels are treated like real analog inputs e g set points totalizing If mathematics is selected an analog signal can no longer be recorded there If the device is a 3 channel device analog input 4 6 can be used as a mathematics channel Note Analog input 1 cannot ...

Page 39: ...erage or sum total of two or more channels Mathematics channels are treated like real analog inputs set points etc Function g Only for Mathematics Sum or Average of channels y1 to y2 Picklist Not Used Sum Average Signal y1 Only for Mathematics y1 signal that should be linked to another signal Picklist Analog Input x Note Other mathematics channels can be used for the calculation if their channel n...

Page 40: ...n of error voltage by using thermostated comparison points Comparison Temp Only for Comparison Point External Settings for the external comparison temperature only when connecting thermocouples directly Submenu Meas Value Correct Offset Correction value this can be entered before further evaluation takes place e g in order to smooth out measurement chain tolerances Follow these instructions 1 Meas...

Page 41: ...menu Fault Mode Settings that lay down how this channel is to react under fault conditions e g cable open circuit over range Fault Switches switches the selected relay under fault conditions The terminal numbers are shown in brackets Picklist Not Used Relay x Term xx xx Save Event stores an event in the event memory when a fault condition occurs Picklist No Yes Cable Open Circ The cable open circu...

Page 42: ...ds on the set failsafe mode of this channel A relay is switched if set Analysis if the error is pending during the entire analysis period the value in the analysis is invalid If there was at least 1 valid value the result of the analysis is valid All other settings or are displayed Channel name is highlighted in red Status F is displayed Value is totalized A relay is switched if set Analysis if th...

Page 43: ...H 5 Enter unit dimension 5 Where necessary enter current counter reading to continue a total yearly counter 5 Enter event text for status change from L H 6 End 6 Enter event text for status change from H L 6 Select the number of decimal places 6 Select display for counter type e g daily counter 6 Enter event text for status change from H L 7 End 7 Enter pulse factor 7 End 7 Where necessary enter c...

Page 44: ...ning time of a pump is to be saved activate Operational Time here and Daily Analysis under Signal Analysis Event Operation Time both the on off events and the operating time of an external unit are recorded and stored Channel Ident Measurement point name e g Pump or description of the function of this input e g Fault message 10 character entry Factory setting digital 1 Additional Info Note Only av...

Page 45: ... key Only active for On Off Event and Event Operation Time functions Save Event Determines whether the condition change from low to high or high to low is stored in the event list Note increased memory capacity needed Only active for On Off Event and Event Operation Time functions Picklist Yes No Event Text L H Description of condition change from low to high Event text is stored e g start filling...

Page 46: ...et Point The upper value of the set measuring range is displayed here Set Point Analog set point in the preset engineering unit e g in C bar etc Counter alarm set point in the engineering units set up e g m piece Hysteresis Type Only for Analog Input x with Upper or Lower Set Point Percentual set hysteresis in Absolute enter hysteresis in the preset engineering units e g in C bar etc Hysteresis On...

Page 47: ... is shown on the display or stored in the event list Only available when LV Messages is set to Display Acknowledge or Save Event is set to Yes 22 character entry Save Cycle Normal save in normal save cycle Alarm Cycle fast storage during an alarm violation e g every second Attention requires higher memory capacity Save cycles are set up in the menu Basic Settings Copy Settings Copies the setup of ...

Page 48: ...lly Caution All the channels are always displayed in the curve Picklist channel x Switched Off Analog Input x Digital Input x Submenu Bargraph Specify the channels that should be displayed in the bar graph If no channels are assigned the device assigns the channels automatically Picklist channel x Switched Off Analog Input x Digital Input x Submenu Digital display Specify the channels which should...

Page 49: ...es preset here Picklist No External 1min 12h Day Calculates daily quantities and operation times Picklist no off yes on Month Calculates monthly quantities and operation times Picklist no off yes on Total year count Calculates quantities and operation times Yes analysis time cycle is one year No Total the analysis is continuous from the time of the last reset useful as a totalizer Synchron time Ti...

Page 50: ...ts individual address 0 99 Factory setting 1 Submenu Serial interface Set up required if you are using the RS232 or RS485 unit interface Fig 36 Set up Communication Serial interface Type Selection as to which interface is being used RS232 or RS485 Baudrate Transmission speed Baudrate must be the same as the settings for the provided PC software Picklist 1200 to 115200 Data bits Please check that s...

Page 51: ... form corresponds to syntax e g 192 168 100 002 Port Please check that settings are compatible with the PC settings Fixed settings cannot be changed Port preset at the factory to 8000 Note The port 8000 must be opened on the Firewall of the accessing PC with Web server function open the port 80 too Call your system administrator Subnetmask Please input the subnetmask given by your network administ...

Page 52: ...r Firefox on a PC Maximally 4 user can have access to the unit via Web server at the same time Note The port 80 must be opened on the Firewall of the accessing PC Call your system administrator A physical web link must be established via LAN or Internet to display the values on the web browser of a PC Fig 39 Remote monitoring with web browser The desired IP address of the unit must be entered in t...

Page 53: ...actFlash card functions PRESET Caution Returns all parameters to the factory default setup The internal memory contents is deleted Picklist No Yes Note Can only be changed using the service code Screen Saver Off on Alarm the screensaver is automatically deactivated in an alarm condition e g limit value cable open circuit etc Always On the screensaver remains switched on even in the event of an ala...

Page 54: ...n menu 6 5 1 Main menu Signal display Changes the display mode e g curve display bar graph digital display or event list The various display modes have no influence on the signal recording Note You can change between the various display modes using U and T Fig 42 Main menu Signal display ...

Page 55: ...total screen signal display Split zones Each channel is displayed in its own chart zone Accuracy of the plot is not influenced in this display mode Fig 44 Split zones signal display Bar graph Display of the active analog measured values as bar graphs including values The digital input is displayed as a status or counter operating time counter Fig 45 Bar graph signal display ...

Page 56: ...re are listed in the correct time sequence Fig 47 Events signal display Measurement point identifier Listing of the 10 character channel identifier together with additional 13 character information text e g additional measurement tag numbers identification system in power stations etc Note Only visible if With add channel info is selected under Set up Basic settings Display Channel ident Fig 48 Me...

Page 57: ... min value max value average value and if applicable the integrated meter reading are output Integration Analysis option Fig 49 Main menu Signal analysis Once an analysis is selected it appears on the display 6 5 3 Main menu Search in trace Search for events or times in the internal memory Fig 50 Main menu Search in trace Search in trace menu items Description Factory setting bold marked Search cr...

Page 58: ...ossible Search filter For a better overview a search can be conducted looking for specific events e g only set up changes In the standard all events are shown Function only possible for search criterion Search for events Picklist All events Alarm limit violation On off events Setup change Power on off Service CompactFlash card Time span Select the times where the events are to be searched for Func...

Page 59: ...rim your new unit to optimum operation all possible operating parameters are accessible see see Section 6 4 6 5 6 Main menu Set contrast You can set the viewing angle upwards or downwards to an optimum contrast depending on the installation height 6 5 7 Main menu Diagnostic unit information Unit information and service functions for a swift unit check The following functions are possible CompactFl...

Page 60: ...y skilled and trained personnel Caution Malfunctions possible if not performed correctly Normal trending is interrupted for the complete time that this function is operational This is also identified in the event list Note Protection via a service code to prevent unintentional release Protocols Boot log Only for service purposes Error log Only for service purposes Note Protection via a service cod...

Page 61: ...copied block by block to the CompactFlash card Tests are also made to determine whether the data has been written onto the CompactFlash without any errors The same happens when storing the data on the PC with the PC software contained in the scope of delivery The data monitored against manipulation is available here If you wish you can export this data into other programs such as MS Excel without ...

Page 62: ...ansfer to the provided PC software Fig 56 Data transfer to the provided PC software Data can be transferred to the installed PC software in one of the following ways Using USB RS232 485 or Ethernet Communication and download of data to PC using the function Read out Read measured values using interface Modem Save the data to CompactFlash in the unit using the function Main menu CompactFlash CF fun...

Page 63: ...OM of the provided PC software Fig 57 Data analysis at PC 6 7 3 Viewing data in a spreadsheet e g MS Excel Fig 58 Data analysis in spreadsheet Select open format csv comma separated values as the save mode in the unit under Set up Basic settings External memory Save as to be able to open saved data directly in the spreadsheet for analysis and printout Note To open the data directly in MS Excel sel...

Page 64: ...ast version 2 00 00 or higher Is this not the case please contact the manufacturer Please hold the release code which you have received from the manufacturer ready see delivery order It is necessary to read out the unit parameters before beginning The unit s settings must be stored in the PC software database Please make sure that the unit is connected with a communication cable The communication ...

Page 65: ...pply 51009211 Terminal pluggable 6 pole for analog input 51009214 Terminal pluggable 3 pole for relay 51009215 Terminal pluggable 6 pole for relay 71062537 Terminal pluggable 5 pole for digital I O 71043991 CompactFlash CF memory card 128 MB 51009640 CompactFlash CF memory card 256 MB 71007465 Cable USB A USB B 2 m 6 56 ft RXU10 A1 Cable set for connection PC or modem RSG30A H1 Field housing IP65 ...

Page 66: ...duced if Limit values events are saved or monitored Signal analyses are activated Digital inputs are active Fig 60 Diagnostic unit information Unit information Calibration Calibration must only be carried out by skilled and trained personnel Caution Malfunctions possible if not performed correctly Normal trending is interrupted for the complete time that this function is operational This is also i...

Page 67: ...the service department of the supplier No data on the CompactFlash card Setup change Software update upgrade CF card defective CPU defective Save the data onto a data carrier before any changes to the setup Save measured values onto a data carrier before any changes to the software Replace the CF card use genuine cards from the manufacturer Accessories see Section 8 Please replace the CPU or call ...

Page 68: ...ircuit Please check the digital input configuration Replace the power supply card or call the service department of the supplier Analog input shows This means cable open circuit The signal lines are incorrectly connected or not connected The input signal does not correspond to the configured signal The sensor is defective Please check the connections Please check the input signal and the configura...

Page 69: ...oard plug for RS485 F RSG30X A2 Analog board channel 4 6 with connector board connector G RSG30X A1 Analog board channel 1 3 I RSG30X NA Power supply 100 230 V AC 10 1 x digital input up to device number 9B021C04267 I RSG30X NB Power supply 100 230 V AC 10 3 x digital input as of device number 9B021C04268 I RSG30X NC Power supply 24 V AC DC 1 x digital input up to device number 9B022E04267 I RSG30...

Page 70: ...erface and CompactFlash socket A B C D E F G Operating language package Standard German English Central western Europe German English French Spanish Italian Dutch Northern Europe German English Danish Swedish Eastern Europe German English Polish Russian Czech Slovak America German English French Spanish American Portuguese Japan German English Japanese China German English Chinese A Internal memor...

Page 71: ... 0 0 and higher BA194R 09 10 05 01 01 00 02 2006 Software revision V1 20 0 0 and higher BA194R 09 02 06 01 02 00 10 2006 Software revision V1 21 2 0 and higher BA194R 09 11 06 02 00 00 11 2007 Software revision Mathematic function included 3 digital inputs V1 23 0 0 and higher BA194R 09 10 07 02 01 00 03 2008 Software revision 1 5 V analog input V1 23 2 0 and higher BA194R 09 03 08 02 02 01 05 200...

Page 72: ...0 to 200 C 328 to 392 F GOST Cu50 200 to 200 C 328 to 392 F GOST Pt50 200 to 850 C 328 to 1562 F GOST 4 wire 0 20 oMR 3 wire 0 20 oMR 0 8 K 2 wire 0 20 oMR 1 5 K Cu53 50 to 180 C 58 to 356 F GOST Pt46 200 to 650 C 328 to 1202 F GOST 4 wire 0 30 oMR 3 wire 0 30 oMR 0 8 K 2 wire 0 30 oMR 1 5 K Thermocouples TC Type J Fe CuNi 210 to 999 9 C 346 to 1832 F IEC581 1 Type K NiCr Ni 200 to 1372 C 328 to 2...

Page 73: ...easured variable Limit values steady state without destroying input Cable open circuit detection line influence temperature compensation Current Maximum permitted input voltage 2 5 V Maximum permitted input current 50 mA 4 20 mA range with cable open circuit monitoring to NAMUR NE43 Activate deactivate the 4 20 mA loop monitoring as per NAMUR recomendation NE43 On activation 3 8 mA Under range ind...

Page 74: ...olated from the system and the inputs testing voltage 500 V The ground of the auxiliary voltage and the ground of the digital input are electrically interconnected Output voltage Approx 24 V max 28 V Output current Maximum 250 mA short circuit proof not stabilised 10 2 2 Relay outputs Alarm relay 1 Alarm relay with changeover contact Standard relay 3 relays with NO contact for limit value messages...

Page 75: ... can be used for program transmission and unit configuration printers or modems cannot be connected here Ethernet interface option Rear mounted Ethernet interface 10BaseT plug type RJ45 connection via shielded cable allocation of IP address via setup menu in unit The unit can be connected to units in an office environment with this interface For safe spacing distances observe the office equipment ...

Page 76: ...ion Position of use as per DIN 16 257 NL 90 30 10 5 2 Installation instructions Panel mounting see Section 3 Installation depth approx 171 mm 6 73 inch incl terminals and fastening clips Panel cutout 138 1 x 138 1 mm 5 43 0 04 x 5 43 0 04 inch Panel thickness 2 to 40 mm 0 08 to 1 57 inch Maximum point of view range From the display center 50 to the left and right 20 upward 30 downward Securing to ...

Page 77: ...ignal 2 kV power supply Surge on power line IEC 61000 4 5 2 kV asymmetrical 1 kV symmetrical Surge on signal line IEC 61000 4 5 1 kV asymmetrical with external protection element Conducted HF IEC 61000 4 6 150 kHz to 80 MHz 10 V Power failure IEC 61000 4 11 20 ms 0 Voltage variation IEC 61000 4 11 40 0 Emission To IEC 61326 Class A operation in industrial environment Interference voltage Power lin...

Page 78: ...ia door plastic ABS Housing fiberglass reinforced plastic PC Protective cover in front of display plastic PC 10 8 Human interface 10 8 1 Display elements Type LC color graphic display Size screen size measured diagonally 120 mm 4 7 Resolution 76 800 pixels 320 x 240 pixels Y X 137 9 mm 5 43 21 mm 0 83 150 mm 5 9 36 1 mm 1 42 138 mm 5 43 1 0 04 138 mm 5 43 1 0 04 86 5 mm 3 4 144 mm 5 67 144 mm 5 67...

Page 79: ...ured values date and time 10 8 2 Operating elements Keyboard Option of operation and configuration via 7 push buttons on the front side in interactive dialog with the screen or using the provided PC software Display of integrated operating instructions at the push of a button 10 8 3 Data storage Save cycle Selectable save cycle 1s 2s 3s 4s 5s 10s 15s 20s 30s 1min 2min 3min 4min 5min 10min 30min 1h...

Page 80: ...e Frequent entries in the events list reduce the memory availability Internal memory weeks w days d hours h CompactFlash 128 MB weeks w days d hours h CompactFlash 256 MB weeks w days d hours h Analog inputs Save cycle 5 min Save cycle 1 min Save cycle 30 s Save cycle 10 s Save cycle 1 s 1 68 w 5 d 0 h 15 w 1 d 23 h 7 w 4 d 11 h 2 w 3 d 19 h 1 d 18 h 3 34 w 2 d 12 h 7 w 1 d 20 h 3 w 4 d 10 h 1 w 1...

Page 81: ...directives The manufacturer confirms successful testing of the device by affixing the CE mark 10 9 2 UL listed for Canada and USA The device was examined by Underwriters Laboratories Inc UL in accordance with the standards UL 61010 1 and CSA C22 2 No 61010 1 and listed under the number E225237 UL 10 9 3 Other standards and guidelines CSA approval CAN CSA C22 2 No 61010 1 04 Safety requirements for...

Page 82: ...trast 59 Control Input 44 Copy Settings 41 47 Copy setup to CF 59 Correction RWT 53 Curve Display 48 D Damping Filter 40 Data analysis 63 Data bits 50 Data storage 79 Data transfer to PC software 62 Date format 33 Date NT ST 33 Date time setup 33 Day 49 Decimal Point 39 45 Decimal separator 32 Degree of protection 77 Delete CF 59 Description H 45 Description L 45 Design dimensions 78 Diagnostic un...

Page 83: ... Operation 53 NT ST changeover 33 NT ST region 33 O Offline data check analysis and printout 63 Offset 40 On Off Event 44 Operating Mode 47 53 Operational time 35 Orientation 76 P Panel mounting 9 Parity 50 PC database 25 Plot Type 39 Port 51 Port address 25 Power consumption 75 PRESET 53 Program name 60 66 Pulse Counter 44 Pulse length 74 R Range 38 Range Start 39 46 Real time clock RTC 81 Rear i...

Page 84: ...ge temperature 76 Subnetmask 51 Supply voltage 15 75 Switches Output 46 Switches output 35 Synchron time 49 T Technical improvement 5 Temp units 32 Temperature drift 76 Terminals 47 Time Delay 46 Time format 33 Time NT ST 33 Time span 58 Total Year Count 45 Total year count 49 Totalization 41 Transport and storage 8 Type 46 50 U Unit address 50 Unit identifier 32 Unit information 60 66 Update CF 5...

Page 85: ......

Page 86: ...www endress com worldwide BA194R 09 en 13 10 51009564 FM SGML6 0 ProMoDo ...

Reviews: