Deltabar PMD75B HART
Technical data
Hauser
75
T
p
T
a
80
176
85
185
90
194
95
203
100
212
105
221
110
230
73
85
163
185
62
144
50
122
T
a
[°C]
[°F]
T
p
[°C]
[°F]
15
59
27
81
38
100
A0043580
T
a
Maximum ambient temperature at the manifold
T
p
Maximum process temperature at the manifold
Oxygen applications (gaseous)
Oxygen and other gases can react explosively to oils, grease and plastics, such that, among
other things, the following precautions must be taken:
• All components of the plant, such as the measuring devices, must be cleaned according
to national requirements.
• Depending on the materials used, a certain maximum temperature and a maximum
pressure must not be exceeded for oxygen applications.
Cleaning of the measuring device (not device accessories) is offered as an optional service.
• p
max
: 80 bar (1
200 psi)
• T
max
environment: 60 °C (140 °F)
Process temperature range
(temperature at
transmitter)
Measuring device without a manifold
• –40 to +85 °C (–40 to +185 °F)
Lower temperatures are optionally available.
• Pay attention to the process temperature range of the seal
Measuring device with a manifold
The maximum permitted process temperature at the manifold is 110 °C (230 °F) (limited
by IEC standard).
For process temperatures >85 °C (185 °F) where non-insulated side flanges are installed
horizontally on a valve manifold, a reduced ambient temperature applies up to a maximum
ambient temperature calculated according to the following formula:
T
Ambient_Temperature_max
= 85 °C − 2.8 ⋅ (T
Process_Temperature
− 85 °C)
T
Ambient_Temperature_max
= 185 °F − 2.8 ⋅ (T
Process_Temperature
− 185 °F )
T
Ambient_Temperature_max
= maximum ambient temperature in °C or °F
T
Process_Temperature
= process temperature at a manifold in °C or °F
Process temperature range,
seals
• FKM: –20 to +85 °C (–4 to +185 °F)
For PN > 160 bar (2
320 psi): T
min
–15 °C (+5 °F)
• PTFE: –40 to +85 °C (–40 to +185 °F)
• FKM, cleaned from oil+grease: –10 to +85 °C (+14 to +185 °F)