Notes on Safety
Approved usage
The Cerabar S is a pressure transmitter used for measuring gauge or absolute pressure
depending on the version. You can display the measured pressure value as a level value
using the Commuwin II operating and display program or using the handheld operating
terminals for HART or INTENSOR.
Mounting,
commissioning,
operation
The Cerabar S has been designed to operate safely in accordance with current technical,
safety and EU standards. If installed incorrectly or used for applications for which it is
not intended, however, it is possible that application-related dangers may arise, e.g.
product overspill by incorrect installation or adjustment. For this reason, the instrument
must be installed, connected, operated and maintained by personnel that are authorised
by the user of the facility and who are suitably qualified. The manual must have been
read and understood, and the instructions followed. Modifications and repairs to the
device are permissible only when they are expressly approved in the manual. Pay
attention to the technical data on the nameplate.
Explosion hazardous
area
The measuring system used in the explosion hazardous area must comply with all existing
national standards. The instrument can be supplied with the following certificates as listed
in the table. A separate Ex-documentation is enclosed with the device and is an integral
part of this documentation. The installation regulations, connection values and Safety
Instructions listed in this document must be observed. The certificates are designated
by the first letter of the order code on the nameplate (see table below).
•
Ensure that technical personnel are adequately trained.
•
All measurement and safety regulations which apply to the measuring point are to
be observed.
Code
Certificate
Explosion protection
R
Standard
None
C
ATEX
ATEX II 3 G EEx nA II T5/T6
G
ATEX
ATEX II 1/2 G EEx ia IIC T4/T6
I
ATEX
PMP 731/PMP 635: ATEX II 2 G EEx d IIC T5/T6
PMC 731/PMC 631: ATEX II 2 G EEx d [ia] IIC T6
Q
FM
PMP 731/PMP 635:
FM Explosion proof Class I, II, III Div. 1, Groups A…G
O
FM
FM IS Class I, II, III, Div. 1, Groups A…G
U
CSA
PMP 731/PMP 635:
CSA Explosion proof Class I, II, III, Div. 1, Groups B…G
S
CSA
CSA IS Class I, II, III, Div. 1, Groups A…G
W
TIIS
TIIS IS Ex ia IIC T4/T6
Certificates for applications in
explosion hazardous areas
HAUSER
CERABAR S PMC/PMP
Order No. PMC xxx –
Order No. PMP xxx –
Cerabar S
Notes on Safety
Hauser
7