Cerabar M
Hauser
23
Performance characteristics – ceramic diaphragm
Reference accuracy
Reference accuracy comprises non-linearity after limit point setting, hysteresis and non-reproducibility as per
IEC 60770.
PMC41, PMC45:
Note!
In the case of overpressure measurement using absolute pressure sensors, the accuracy can be affected by
fluctuating ambient air pressure.
Thermal change of the zero
output and the output span
4...20 mA
4...20 mA HART, PROFIBUS PA
Temperature coefficient (T
K
)
for zero output and output
span
If the value for the temperature coefficient exceeds the value for the thermal change, the thermal change
automatically applies.
4...20 mA
4...20 mA HART, PROFIBUS PA
Measuring cell
% of the set span
100 mbar, 400 mbar
("1C", "1F", "5C", "5F" and "2F" version for
feature 30 "Sensor range"; MWP; OPL)
• ±0.2 x TD
• Optional
1
): ±0.1 % non-linearity of set span x TD
1)
→
See also Page 67 ff, chapter "Ordering information" section, feature 40 "Calibration; Unit", version "C"
1 bar, 4 bar, 10 bar, 40 bar
• ±0.2
• Optional
)
: ±0.1 % non-linearity of set span
–10...+60 °C
(+14 to +140°F)
–40...–10 °C, +60...+85 °C
(-40 to +14°F, +140 to +185°F)
+85...+125 °C (+185 to +257°F)
(only PMC45)
% of the set span
X
⎯
⎯
•
±
(0.3 x TD + 0.3)
⎯
X
⎯
•
±
(0.5 x TD + 0.5)
⎯
⎯
X
•
±
(0.8 x TD + 0.8)
–10...+60 °C
(+14 to +140°F)
–40...–10 °C, +60...+85 °C
(-40 to +14°F, +140 to +185°F)
+85...+125 °C (+185 to +257°F)
(only PMC45)
% of the set span
X
⎯
⎯
•
±
(0.2 x TD + 0.2)
⎯
X
⎯
•
±
(0.4 x TD + 0.4)
⎯
⎯
X
•
±
(0.6 x TD + 0.6)
–10...+60 °C
(+14 to +140°F)
–40...–10 °C, +60...+85 °C
(-40 to +14°F, +140 to +185°F)
+85...+125 °C (+185 to +257°F)
(only PMC45)
% of URL/10 K
X
⎯
⎯
•
±
0.15
⎯
X
⎯
•
±
0.2
⎯
⎯
X
•
±
0.25
–10...+60 °C
(+14 to +140°F)
–40...–10 °C, +60...+85 °C
(-40 to +14°F, +140 to +185°F)
+85...+125 °C (+185 to +257°F)
(only PMC45)
% of URL/10 K
X
⎯
⎯
•
±
0.08
⎯
X
⎯
•
±
0.1
⎯
⎯
X
•
±
0.12