background image

Assembly/ User Instructions 
 
 
 
 
 
 
 

 

These assembly diagrams are intended as a guide – if in doubt consult a qualified electrician.  

 

 

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 

 
 
 
 
 
 

 

 
 

Y11 139 

Diagram A 

1. 

   

Decide on the position of the light fitting / or remove 

existing light fitting. Take a note of the position of 
the electrical connections. Ensure there is a solid 
mounting surface, preferably a wooden joist or joist 
bridge to support the weight of the light fitting.  
 

2.   See 

Diagram A

. Remove the fixing bracket by 

undoing the 2 side screws (1), retain for re-use. 

 

3.    Use the fixing bracket (2) as a template to mark the 

screw holes, mark the screw holes and secure to 
the ceiling with the screws (3) supplied. 

 

4. 

   

Diagram B

.  The length of the `drop` may be 

reduced by shortening the cable / support wires.  If 
you want to reduce the overall length of the fitting it 
is essential that this is done before the fitting is 
mounted to the ceiling and / or connected to the 
mains supply. To do this, shorten the length of the 
support wires by pushing up the centre of the 
support mechanism (which acts as a clutch) and pull 
the wire up through and into the ceiling cup. When 
you reach the desired overall length release the 
centre clutch – this will then grip the support wire. 
We recommend that the minimum distance between 
the ceiling cup and the top of the fitting is 100mm. 
The cable must now be shortened and the excess 
cable cut and re-connected to the terminal block. To 
do this, firstly take a note of the position of the 
cables in the terminal block then feed the cable up 
through the ceiling cup (grub screw) entry hole, cut 
off the excess cable and re-connect to the terminal 
block. Move the cable anchor down the cable – from 
(A) to (B).This is a strain relief device and must be 
used.  NOTE: 

The electric cable must always be 

longer than the support wire to prevent strain 
being placed on the cable

. Secure the grub screw 

onto the cable.

 

 

5.     Support your fitting and connect the house wiring to 

the terminal block (4) – see 

wiring details. NOTE:

 

This is a Class I fitting and

 

must be earthed

. The 

4

th

 terminal block connector is used for the “loop” 

wires of the “Ring Circuit”. There may be more than 
one set of cables in the “loop” connections. If there 
is a “Ring Circuit” and you do not understand the 
connections you must consult an electrician.   Any 
loose terminal blocks –not secured to ceiling cup - 
should always be covered with 2 layers of good 
quality insulation tape.          

  

6. 

  Secure the fitting back onto the fixing bracket with 

the 2 side screws (1), removed in 2 above. Make 
sure that all the internal cables and connections are 
inside the ceiling cup taking care not to trap or strain 
the internal cables.

 

 

7.   Fit the decorative drop assemblies (5) as shown. 

 

8. 

   Fit the bulbs (6) into the lamp holders being careful 

not to touch the bulbs with your bare hands – use a 
cloth or gloves to insert the bulbs. 

NOTE; Never fit 

bulbs of a higher wattage or of a type other than 
those provided / specified on the label (as these 
may cause overheating and damage the fitting). 

 

9. 

  T

urn on the power and test. 

 
 

Diagram B 

Endon lighting Ltd. 
Leeds. 
UK 
LS9 0SE 

WIRING DETAILS 

Cable entry 
tube with grub 
screw 

Support wire clutch 
mechanisms 

X 15pcs 

X 10pcs 

X 5pcs 

X 1pc 

(A) 

(B) 

Reviews: