SET
SET
ET1411
ENDA
OUT
°F
°C
ET
1
411-E-06-R
2/2
The lower limit
of the setpoint.
Control mode
While holding key OUTPUT setpoint value appears and by using and keys
the value can be adjusted.
C.typ
Programming Mode
Run Mode
Process
Value
30.0
29.9
30.0
o.lol
1000
If both keys are pressed and held for 3 seconds,
programming mode is entered.
The offset value
for the output
o.off
Output
hysteresis
o.Hys
Decimal place
T
he upper limit
of the setpoint.
o.uPl
Unit
22.0
If both keys are pressed,
run mode is entered.
ou
Cn
Security parameter
for configuration menu
A.
-
Cn
Security parameter
for output setpoint value
A.ou.S.
A.
-
ou
Security parameter
for output menu
S.Cod
Access code for security menu.
This parameter should be
321
.
o.PPF
o.PPn
On time for the output
in the case of
probe failure.
Off time for the output
in the case of
probe failure.
Temperature unit
dres
Menu of Output control parameters
o.HYS
o.LoL
o.uPL
o.oFF
Output hysteresis
The lower limit of the setpoint.
T
he upper limit of the setpoint.
The offset value for the output
ou
-60.0
-20.0
0.1
o.LoL
150.0
MIN
UNIT
MAX
DEF.
SET
o.PPn
On time for the output in the case of probe failure.
o.PPF
Off time for the output in the case of probe failure.
A. ou
-
A.ou.S.
A. Cn
-
Security parameter for
menu of output control
= Menu is invisible.
NonE
P.yes
P.no
= Parameters of menu are changeable.
= Parameters of menu are only visible.
= Setpoint value is changeable.
= Setpoint value is only visible.
P.yes
P.no
Security parameter for
menu of configuration
Security parameter for
output setpoint value
Unit
dres
Temperature unit
Decimal place (
no
=
no decimal point,
22
°C
yes
= with
decimal point,
22.3
°C )
C.tyP
Control mode (
Heat
= Heating cotrol
Cool
°C °F °C
=Cooling control)
o.uPL
-60
°C
°C
150
°C
°C
0
20.0
2
20.0
0
255
Min.
0
0
255
Min.
1
Heat
Cool
Heat
no
yes
no
Menu of Configuration
Cn
Menu of Parameter security
SE
PARAMETER TABLE
Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode
.
When held down for a
few seconds, the change rate accelerates.
Used for selecting parameters and decreasing the setp
oint value
in the programming mode and for decreasing the setpoint value in the run mode
.
When held down for a few
seconds, the change rate accelerates.
OUT
LED
FAHRENHEIT
LED
Displayed process value in the run mode, parameter name or value in programming mode.
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding key, setpoint value of the
selected parameter appears and by using and keys the value can be adjusted.
Pfa
Means, thermostat probe is short circuit.
PsC
Means, thermostat probe is broken.
Error Messages
Temperature value is higher than the scale.
Temperature value is lower than the scale.
Se
SET
SET
SET
SET
SET
SET
SET
SET