background image

Holding Register 
      Addresses

Data 
Type

Data Content

Parameter 
    Name

Read/Write
Permission

Digital input types .0=

nd

;1=

EA

;2=

SA

;3=

df

Set point

Set point upper limit

Upper level alarm

Set point lower limit

Lower level alarm

Offset cooling value

Cooling differential

Alarm differential

Digital input delay

Delay time for the compressor after power is on.

On time for the compressor output in the case of probe failure

Off time for the compressor output in the case of probe failure 

Defrost duration
The time between 2 consecutive defrosts.

Delay time for defrosting after power is on.

After the cooling process of cooling start-up delay

5Et

uPL

A.uPL

LoL

A.LoL

oFF

Hy5

A.HY5

5nd

d.inp

ddi

C.Pon

C.Fo5

C.PPn

C.PPf
d.dur

d.int

d.dpo

d.drE

A.dfl

A.dpo

Delay time required for the compressor to restart following  a stop.

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write
Read / Write
Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Data 
Type

Measured ambient, temperature value (

°

C / 

°

F)

*

 Holding and Input Register parameters of type integer, those “signed integer” is defined as the decimal port of and associated with these parameters. (So,”14.0” is a parameter 

value of “140” will be read in). Relevant parameters for a period of “mm:ss” type ones in seconds, ”hh:mm” while those species defined in minutes.

Compressor  output status (0=OFF; 1=ON)

      Coil
Addresses

Decimal

Hex

Data 
Type

00d

0x00

Bit

1.4 COILS

01d

0x01

Bit

Temperature unit.  OFF = 

°

C

  ,  ON = 

°

F

Unit

02d

0x02

Bit

Decimal point . OFF=

no  , 

ON=

YE5

D.PNT

03d

0x03

Bit

Digital input polarity. OFF = 

cL  , 

 ON = 

oP

Dpo

04d

0x04

Bit

Smart Defrost selection.   OFF = 

n

o

 ,  ON= 

YE5

D.5mt

Defrost type selection  OFF = 

ELC

  ,  ON = 

GAS

Dd5p

05d

0x05

Bit

06d

0x06

Bit

dpon

07d

0x07

Bit

DtYp

Data Content

Read/Write 
Permission

Parameter 
    Name

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Read / Write

Dripping (discharge) time

Read / Write

ddrt

Decimal

Hex

0000d

0001d

0002d

0003d

0004d

0005d

0006d

0007d

0008d

0009d
0010d

0011d

0012d

0013d

0014d

0015d

0016d

0017d

0018d

0019d

0021d

0x0000

0x0001

0x0002

0x0003

0x0004

0x0005

0x0006

0x0007

0x0008

0x0009
0x000A

0x000B

0x000C

0x000D

0x000E

0x000F

0x0010

0x0011

0x0012

0x0013

0x0015

word

word

word

word

word

word

word

word

word

word
word

word

word

word

word

word

word

word

word

word

word

1.1 HOLDING REGISTERS

Input Register 

Addresses

Decimal

Hex

1.2 INPUT REGISTERS

0000d

0x0000

word

--

Discrate Inputs 

Addresses

Decimal

Hex

1.3 DISCRATE INPUTS

0000d

0x0000

bit

--

word

0x0014

0020d

0001d

0x0001

bit

--

ENDA EDT2423A DIGITAL THERMOSTAT MODBUS PROTOCOL ADDRESS MAP

Data Content

Parameter 
    Name

Read/Write
Permission

Read

Data 
Type

Data Content

Parameter 
    Name

Read/Write
Permission

Read

Read

Defrost output status (0=OFF; 1=ON)

A.tYP

08d

0x08

Bit

Alarm configuration.  OFF = 

Ab5

  ,  ON = Relative alarm  

rEF

Read / Write

Defrosting process begins with energy. OFF =  

no 

, ON = 

YE5

 

During defrost, display configuration. OFF = 

Lc

 , ON = 

rE

                                                       

Defrost stop temperature

Time delay to display alarm message after alarm is on.

Time delay to display alarm message after power is on.

F.5tp

F.Pon

f.5td

Read / Write

Read / Write

Read / Write

Read / Write

F.hy5

0022d

0023d

0025d

0x0016

0x0017

0x0019

word

word

word

word

0x0018

0024d

Required delay time for fan to be powered up.

Required delay time for fan to be powered up after defrost.

Fan stop temperature.

Fan differential.

Measured defrost sensor, temperature value (

°

C / 

°

F)

0001d

0x0001

word

--

Read

0002d

0x0002

bit

--

Read

Fan output status (0=OFF; 1=ON)

F.Con

09d

0x09

Bit

F.c5t

10d

0x0A

Bit

Read / Write

Read / Write

F.d5t

11d

0x0B

Bit

Read / Write

F.ctr

Fan operates with thermostat. OFF=

no

 , ON=

yE5

Fan operations when compressor stop. OFF=

no

 , ON=

yE5

Fan operation during defrost process. OFF=

no

 , ON=

yE5

Fan control depending on room temperature. OFF=

no

 , ON=

yE5

4/4

ENDA

TM

      EDT2423A-E-05-201016

SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.

Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu  34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx.    Fax : +90 216 365 74 01
url : www.enda.com.tr

--

Read

0002d

0x0002

word

All controls output status

*All outputs will be displayed in the word as compressor (0.bit) defrost (1.bit) fan (2.bit).

12d

0x0C

Bit

Read / Write

5LOC

13d

0x0D

Bit

While the keys are locked , set value is adjustable.  OFF = 

no

 ,  ON = 

ye5

Read / Write

14d

0x0E

Bit

15d

0x0F

Bit

Read / Write

Read / Write

16d

0x010

Bit

Read / Write

The keylock active / inactive. OFF= inactive , ON= active

Starting manual defrost or stopping manual defrost. OFF= stopping , ON= starting

Control outputs active / inactive. OFF= active , ON= inactive

The factory setting is loaded.  ON= The factory setting is loaded.  

--

--

--

--

* For Coil at a time should be maximum 16 bit reading / writing.

Summary of Contents for EDT2423A

Page 1: ...ng clamp For removing mounting clamps out the clamp in direction 2 Push the flush mounting clamp in direction 1 as shown in the figure below Then pull 71 5mm 28 5mm Panel cut out 61mm 5mm Flush mounting clamp Panel Rubber packing 2 Depth 77mm 35mm 1 EDT2423A E 05 201016 ENDA INDUSTRIAL ELECTRONICS SN XXXXXXXXX ENDAKEY 230V AC 10 20 50 60Hz 5VA 8 6 8 0 4 0 7 7 0 2 4 2 8 1 2 3 4 5 6 7 8 EDT2412 230 ...

Page 2: ... the user menu is entered afterwards first parameter s name is displayed in the user menu SET While a parameter was selected by pressing to key parameter s value is displayed the displayed this parameter can be changed with keys When the parameter name is shown no action is done after 3 seconds or to the key is pressing again to return to the parameter s name When the parameter name is shown keys ...

Page 3: ...s on 2 0 10 hr min ENDAKEY PARAMETER TRANSFER NOTE 1 No power up required for transfering the parameter by using ENDAKEY For long battery life ENDAKEY must be disconnected from device after the transferring process NOTE 2 Please specify at order ENDAKEY if required d 5mt Smart Defrost selection no Defrost counter between 2 defrost duration decrease irrespective of d int status of the compressor YE...

Page 4: ...0x0011 0x0012 0x0013 0x0015 word word word word word word word word word word word word word word word word word word word word word 1 1 HOLDING REGISTERS Input Register Addresses Decimal Hex 1 2 INPUT REGISTERS 0000d 0x0000 word Discrate Inputs Addresses Decimal Hex 1 3 DISCRATE INPUTS 0000d 0x0000 bit word 0x0014 0020d 0001d 0x0001 bit ENDA EDT2423A DIGITAL THERMOSTAT MODBUS PROTOCOL ADDRESS MAP...

Reviews: