5-3
5 TROUBLESHOOTING
5.4 Alarms
Activation of alarms is by flow switch or MAP
®
switch.
Issue
Solution
Alarm will not shut-off
• The flow switch may be stuck open (energized) by metal
shavings or pipe scale. Disconnect the power, remove
bonnet, and clean the shuttle (see “4.9.2 Flow Switch
(optional)” on page 4-19).
• The MAP
®
switches may require repositioning after a period
of time due to usage. Readjust them as required. See “4.9.1
Magnetic Activated Proximity Switch (MAP
®
Switch)” on page
4-16.
Alarm light does not
operate
Check bulb in alarm light. If the light bulb is good, check
continuity of the alarm circuit according to the wiring
diagram (refer to Figure 2-4 on page 2-7.
Audible Alarm
does not operate
Check for debris in MAP
®
switch or flow switch (see first
item above). Shavings, rocks, and objects can prevent
switches form closing, the alarm will not energize. If
energized (alarm) local and remote will be constant.
Remote Alarm does not
operate
Check the relay located in junction box for proper wiring. The
relay is rated at 5 amps or 3 amps for 120 or 240 volt
systems.