2
Wireless Ceiling Mount Sensor Installation Instructions
Wireless Ceiling Mount Sensor
INSTALLATION
INSTRUCTIONS
WIRELESS SYSTEM OVERVIEW
This illustration shows how each component is easily integrated into the Encelium X Lighting Control System.
Wireless Manager
SSU
Wireless Ceiling
Mount Sensor
W
Wireless Ceiling
Mount Sensor
User Interface
Integrated
Controller
Mount Sensor
Mount Sensor
Ethernet
Wire Key
SENSOR COVERAGE
3.6 m
(12 ft)
3.6 m
(12 ft)
8 ft
(2.4 m)
0
1.5 m
(5 ft)
1.5 m
(5 ft)
0
SIDE VIEW
Standard Range Sensor
TOP VIEW
6.1 m
(20 ft)
6.1 m
(20 ft)
2.4 m
(8 ft)
0
3 m
(10 ft)
3 m
(10 ft)
1.7 m (5.6 ft)
2.7 m (9 ft)
3.3 m (11 ft)
(4.6 m (15 ft)
0
6.1 m (20 ft)
SIDE VIEW
Extended Range Sensor
TOP VIEW
9.1 m
(30 ft)
9.1 m
(30 ft)
12.2 m
(40 ft)
0
3 m
(10 ft)
6.1 m
(20 ft)
3 m
(10 ft)
6.1 m
(20 ft)
0
SIDE VIEW
High Bay Sensor
TOP VIEW
0.9 m (3 ft)
6.1 m (20 ft)
(4.6 m (15 ft)
3.3 m (11 ft)
2.7 m (9 ft)
1.7 m (5.6 ft)
0.9 m (3 ft)
1.5 m (5 ft )
2.1 m (7 ft )
2.7 m (9 ft )
3.6 m (12 ft )
0.9 m (3 ft)
0.9 m (3 ft)
1.5 m (5 ft )
2.1 m (7 ft )
2.7 m (9 ft )
3.6 m (12 ft )
3 m (10 ft)
6.1 m (20 ft)
9.1 m (30 ft)
3 m (10 ft)
6.1 m (20 ft)
9.1 m (30 ft)
45571—EN-SCPPH-0450-ZB
45570—EN-SCPPH-1500-ZB
56302—EN-SCPPH-HB-ZB
0
0
0
Notes:
The sensor must be installed in dry, indoor locations ONLY. Do not install the sensor in damp locations.
Damp locations are defined as: interior locations subject to moderate degrees of moisture, such as basements, barns,
cold-storage warehouses, as well as partially protected locations under canopies, marquees and porches with open roofs. The sensor
provides a 360° coverage pattern. It is recommended that the sensor be installed more than 4 ft (1.2 m) away from
air supply vents.