background image

EMX Industries, Inc. 

Tech support: 216-834-0761 

3/6

 

ULT-PLG_Rev1.8_082619                                    [email protected]

 

 

 

Automatic 
Sensitivity  
Boost 

DIP Switch 8 

The 

Automatic  Sensitivity  Boost

  causes  the  sensitivity  

to  increase  following  initial  detection.  This  feature  is  useful  
to  prevent  dropout  when  detecting  high-bed  vehicles.  
The  sensitivity  returns  to  its  normal  setting  after  the  vehicle 
exits the loop. The decimal point on the ULTRAMETER

 display 

indicates ASB is on. 

ASB Enabled 

on 

ASB Disabled 

off 

 

 

 

 

Presence 

DIP Switch 7  Infinite

 presence mode causes the output to remain in detect 

as long as the vehicle remains on the loop. 

Normal

 presence 

mode causes the output to reset after 5 minutes. 

Do not use 

Normal presence mode for reversing loop applications. 

Normal 

on 

Infinite 

off 

 

 

 

 

Detect-On-Stop

 

DIP Switch 6 

The 

Detect-On-Stop

 (DOS

®

)

 feature requires that a vehicle 

must come to a complete stop over the loop for a minimum of 
1-2 seconds before Output B activates. DOS

®

 will not function 

if in Loop Fault mode.  

Do not use DOS

®

 feature for reversing 

loop applications.

 

DOS

®

 On 

on 

DOS

®

 Off 

off 

 

 

 

 

Output B 

DIP Switch 

Output  B  is  configurable  for  four  possible  modes.  
In 

Pulse  on  Entry/Exit 

mode,  Output  B  will  be  activated  for 

approximately  500ms  when  a  vehicle  is  entering  or  exiting  
the  detection  zone.  In 

B  same  as  A

,  relay  B  has  the  same 

output as relay A.  In 

Loop Fault

 mode, the relay will trigger  

if a loop fault occurs. 

Mode 

Pulse on Entry 

on 

on 

Pulse on Exit 

on 

off 

B same as A 

off 

on 

Loop Fault

 

off 

off 

 

 

 

 

Fail Safe / Secure 

DIP Switch 3 

The 

Fail  Safe

  setting  causes  the  ULT-PLG  to  activate  the 

presence output in the event of a loop failure. The 

Fail Secure

 

setting  will  cause  the  ULT-PLG  not  to  activate  the  presence 
output in the event of a loop failure. 

Do not use Fail Secure 

for reversing loop applications.  

Fail Safe 

on 

Fail Secure 

off 

 

 

 

 

Frequency 
Settings 

DIP Switch 

DIP  switches  2  and  1  are  used  to  assign  the  loop  operation 
frequency.  The  primary  purpose  of  the 

Frequency  Setting

  

is  to  allow  the  installer  the  ability  to  set  different  operating 
frequencies  for  multi-loop  installations  and  is recommended  
to prevent crosstalk/interference from multiple loops. 

Low 

on 

on 

Medium Low 

on 

off 

Medium High 

off 

on 

High 

off 

off 

 

 

 

 