EMX Industries MVP D-TEK Instruction Manual Download Page 7

EMX Industries, Inc. 

Tech support: 216-834-0761 

7/7

 

MVP D-TEK_Rev2.0_081319                                [email protected]

 

 

Troubleshooting

 

 

Symptom 

Possible Cause 

Solution 

Green LED not on  No power 

Check  the  power  supplied  to  the  MVP  D-TEK  on  
pins 1 (white wire) and 2 (black wire). Voltage should 
read between 12-240 VDC/AC. 

Green LED  
fast flash 

Loop wire shorted or not 
connected  

Check the loop resistance with a multimeter to confirm 
a reading between 0.5 ohms and 5 ohms. If reading is 
outside  of  this  range,  replace  the  loop.  The  reading 
should be steady. 
 
Check loop connections to terminals 
 
Momentarily flip the RESET switch down 

Green LED  
slow flash 

Loop wire was previously 
shorted or open 
 

Check the loop resistance with a multimeter to confirm 
a reading between 0.5 ohms and 5 ohms. If reading is 
outside  of  this  range,  replace  the  loop.  The  reading 
should be steady. 
 
Momentarily flip the RESET switch down 

Red LED on 
constantly (stuck 
in detection 
mode) 

Faulty loop 
 
 
Poorly crimped 
connection or loose 
connection 

Perform  a  megger  test  from  loop  lead  to  ground,  
it should be more than 100 megaohms. 
 
Check loop connections to terminals. Verify splices are 
properly soldered and sealed against moisture. 

Detector detects 
intermittently 
when no vehicle 
is on the loop 

Faulty loop 
 
 
Poorly crimped 
connection or loose 
connection 
 
Cross-talk between 
multiple loop detectors 
 
Loop not securely 
installed to prevent 
movement of loop in 
pavement.  

Perform  a  megger  test  from  loop  lead  to  ground,  
it should be more than 100 megaohms. 
 
Check loop connections to terminals. Verify splices are 
properly soldered and sealed against moisture. 
 
 
Set multiple loops to different frequencies 
 
 
Verify that loop is securely installed in pavement and 
that site is in good condition preventing movement of 
loop wires. 

 

 

EMX Industries, Inc. products have a warranty against defects in materials and workmanship for a period 
of two years from date of sale to our customer.  

Warranty 

Summary of Contents for MVP D-TEK

Page 1: ...relays Cautions and Warnings This product is an accessory or part of a system Install the MVP D TEK according to instructions from the gate or door operator manufacturer Comply with all applicable cod...

Page 2: ...0 VDC AC 2 Black Power 12 240 VDC AC 3 Orange Relay 2 NO normally open contact 4 Green Earth Ground 5 Yellow Presence 1 COM common contact 6 Blue Presence 1 NO normally open contact 7 Gray Loop 8 Brow...

Page 3: ...presence output in the event of a loop failure and the detector will not change states on power loss or power up In Fail Secure mode relay 2 will trigger if a loop fault occurs Do not use Fail Secure...

Page 4: ...es the detector to the local inductance field DIP switch settings and frequency setting Momentarily flipping the switch up to check the operating frequency will cause the red LED to flash Each flash r...

Page 5: ...bris from the finished cut with compressed air Place sand over the loop wire to the surface and pack tightly Lay new asphalt GRAVEL OR SOIL INSTALLATION While this is not a recommended installation fo...

Page 6: ...ty level increases from position 0 lowest setting through 9 highest setting Typical applications require a setting of 3 or 4 Any time the sensitivity setting changes momentarily flip the RESET switch...

Page 7: ...the RESET switch down Red LED on constantly stuck in detection mode Faulty loop Poorly crimped connection or loose connection Perform a megger test from loop lead to ground it should be more than 100...