©2019 EMS Ltd. All rights reserved. Page 14 of 16
MK241 Iss 2 20/11/2019 AJM
Operating temperature
-10 °C to 55 °C
Storage temperature
5 °C to 30 °C
Humidity
Up to 95% non-condensing
Supply
2x C Alkaline (Panasonic LR14AD Powerline /
Varta
4014
Industrial)
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and may
result in poor performance.
Supply voltage
2.22 to 3.3 VDC
Current consumption
60 μA
Operating frequency
868 MHz
Output transmitter power
Auto adjusting 0 - 14 dBm (0 - 25 mW)
Signalling
protocol
X2
Dimensions (W x H x D)
195 mm x 205 mm x 45 mm
Weight
0.5 kg
Location
Type A: For indoor use
Max. hold open power size
7
Max. door leaf width
1600 mm
Max. test door mass
160 kg
Max. overload test drop weight
36 kg
Max. test door friction
0.8 Nm
Min. angle between door open
66 °
and closed positions
Note: FireCell WDC is not for use on metal doors.