Enclosures For Lp (propane) Gas Supply Systems

Enclosures for LP-gas supply cylinders shall be ventilated by 

openings at the level of the cylinder valve and at floor level. The 

effectiveness of the opening(s) for purposes of ventilation shall 

be determined with the LP-gas supply cylinder(s) in place. This 

shall be accomplished by one of the following.

a.  One side of the enclosure shall be completely open; or

b.  For an enclosure having four sides, a top and a bottom:

1.  At least two ventilation openings at cylinder valve level 

shall be provided in the side wall, equally sized, spaced 

at 180 degrees (3.14 rad), and unobstructed. Each 

opening shall have a total free area of not less than  

1/2 sq in per pound (2.3 sq. cm/kg) of stored fuel capac

-

ity and not less than a total free area of 10 sq in (64.5 

sq. cm).

2.  Ventilation opening(s) shall be provided at floor level 

and shall have a total free area of not less than 1/2 sq in 

per pound (3.2 sq. cm/kg) of stored fuel capacity and not 

less than a total free area of 10 sq in (64.5 sq. cm). If 

ventilation openings at floor level are in a side all, there 

shall be at least two openings. The bottom of the open-

ings shall be at floor level and the upper edge no more 

than 5 in. (127 mm) above the floor. The openings shall 

be equally sized, spaced at 180 degrees (3.14 rad) and 

unobstructed.

3.  Every opening shall have minimum dimensions so as to 

permit the entrance of a 1/8 in. (3.2 mm) diameter rod.

4.  There shall be a minimum clearance of 2 in. (51 mm) 

between the lower surface of the floor of the LP-gas 

supply cylinder enclosure and the ground.

• 

Cylinder valves shall be readily accessible for hand opera-

tion. A door on the enclosure to gain access to the cylinder 

valves is acceptable, provided it is non-locking and can be 

opened without the use of tools.

• 

The design of the fireplace shall be such that (1) the LP-gas 

supply cylinder(s) can be connected, disconnected and the 

connections inspected and tested outside the cylinder en-

closure; and (2) those connections which could be disturbed 

when installing the cylinder(s) in the enclosure can be leak 

tested inside the enclosure;

• 

Ventilation openings in sidewalls shall not communicate 

directly with other enclosures of the fireplace.

The enclosure for the LP-gas cylinder shall isolate the cylinder 

from the burner compartment to provide:

a.  Shielding from heat radiation;

b.  A flame barrier; and

c.  Protection from foreign material.

Be certain to mount the LP gas cylinder on a flat surface and 

restrain it using a cylinder retaining bracket to prevent it 

from tipping.

NON-LOCKING

DOOR

TOP AND SIDE PARTITION

TO ISOLATE TANK FROM

FIREPLACE

OPENING B

OPENING A

C

1” MAX

5” MAX

TOP AND SIDE PARTITION

TO ISOLATE TANK FROM

FIREPLACE

FIREPLACE POSITIONED

ABOVE TANK ENCLOSURE

FIREPLACE POSITIONED

BESIDE TANK ENCLOSURE

5” MAX

1” MAX

2” MIN

Cylinder 

Size

Opening 

Area A

Opening 

Area B

Recommended 

Dimension C

20lb 

(9.1kg)

20 sq.in. 

(130cm

2

)

10 sq.in. 

(65cm

2

)

34 in.

(863mm)

30lb 

(13.6kg)

30 sq.in. 

(195cm

2

)

15 sq.in. 

(100cm

2

)

34 in.

(863mm)

Note: 

There shall be a minimum clearance of 2 in. (51 mm) 

between the lower surface of the floor of the LP-gas supply 

cylinder enclosure and the ground.

Figure 20

FIREpLACE FRAMING AND INSTALLATION

LP-GAS CYLINDER INFORMATION

Summary of Contents for OLL60FP12SN-1

Page 1: ...DANGER CARBON MONOXIDE HAZARD This appliance can produce carbon monoxide which has no odor Using it in an enclosed space can kill you Never use this appliance in an enclosed space such as a camper te...

Page 2: ...nance See page 27 Tools Needed 1 1 8 inch Allen Wrench 2 Adjustalbe wrenches with range of 1 inch for gas connection 2 Adjustable pipe wrenches 1 Phillips Screwdriver CARTON CONTENTS INDEX NO DESCRIPT...

Page 3: ...PLACE INSTALLATION FRAMING INSTALLATION 14 15 ELECTRICAL SUPPLY 16 GAS SUPPLY 17 LP GAS CYLINDER INFORMATION 18 19 FINISHING 20 22 LIGHTING INSTRUCTIONS 23 MAIN BURNER FLAME CHARACTERISTICS 24 OPERATI...

Page 4: ...Please leave these instructions with the owner for future reference This unit complies with ANSI Z21 97 CSA 2 41 for Outdoor Gas Fireplaces InstallationandrepairshouldbedonebyaQUALIFIEDSERVICE PERSON...

Page 5: ...as can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clos...

Page 6: ...Topaz Clear DG1AB 1 2 in Decorative Glass Droplets Aqua Blue DG1GC 1 2 in Decorative Glass Droplets Glacier Ice DG1SL 1 2 in Decorative Glass Droplets Sangria Luster Note Decorative Glass Droplets ma...

Page 7: ...e changing spud orifice size Instructions to Installer 1 Installer must leave instruction manual with owner after installation 2 Installer must have owner fill out and mail registration card supplied...

Page 8: ...19 3 16 21 5 8 24 10 Figure 2 Mantel Clearances Do not attach combustible material to the mantel of your fireplace This is a fire hazard Figure 1 COMBUSTIBLE MATERIALS No greeting cards stockings or o...

Page 9: ...replace opening 16 in of non combustible material is provided to allow for placement of wall joint in a cooler temperature zone NON COMBUSTIBLE WALL BOARD PROVIDED Framing Header Fireplace Opening 2 1...

Page 10: ...The width of the firebox opening 60 60 F The interior depth of the firebox not shown 19 23 7 8 G The rear exterior width of the firebox not shown 60 60 K Height from the bottom of the box to the gas l...

Page 11: ...NOTICE This fireplace is NOT equipped with an Oxygen Depletion Sensor ODS pilot Installation of the fireplace may be in an open area however it is recommended that this fireplace be installed in an a...

Page 12: ...equires that a flexible fireplace connector cannot exceed three feet in length A flex line connection to the valves is provided The gas shut off valve must be located outside of the unit in an accessi...

Page 13: ...with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 Latest Edition A factory installed junction box is located on the lower right side of the fireplace The...

Page 14: ...eplace Framing Before completing the framing and installing fireplace provide a path for water drainage out of the fireplace Determine if the optional accessory drain pan will be used See Page 12 If t...

Page 15: ...f the control panel with a Phillips head screw driver See Figure 15 Figure 15 d Lift front of burner assembly and tilt upwards and toward the back of the fireplace Retrieve the two supports from insid...

Page 16: ...use A connector for the junction box to accommodate 1 2 in conduit is supplied in the instruction envelope The fireplace receptacle must be connected to an external GFI protected outlet installed nea...

Page 17: ...ct your local authorized installer for installation or relocation Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases The gas lines must be ch...

Page 18: ...en achieved It is also equipped with an excess flow device In order to attain full flow to the fireplace the valve must be in the off position when the cylinder valve is turned on WARNING A fire will...

Page 19: ...r surface of the floor of the LP gas supply cylinder enclosure and the ground Cylinder valves shall be readily accessible for hand opera tion A door on the enclosure to gain access to the cylinder val...

Page 20: ...d in step 7 on page 15 and reinstall the control door and center pivot pin 4 Unscrew the ignitor button and install the AA battery provided in the instruction envelope prior to closing the control doo...

Page 21: ...with screws into the frame and pre drill and counter sink 1 8 in diameter holes into the fireplace face Finish remain ing wall with weather proof wallboard Note Areas where the steel has been formed c...

Page 22: ...een and burner enough media to cover approximately 10 square feet Ensure coverage is even and not thicker in places Some pieces of broken glass may be larger than others It is fine to use these pieces...

Page 23: ...cover s must be removed before use Remove any debris including leaves and insects from the burner area and the bed of crushed glass 1 Before turning on the main gas supply press the ignitor button Ver...

Page 24: ...urs with the burner at the highest setting Any odors remaining after this initial break in will disappear with continued use Flames from the main burner should be visually out before the weather door...

Page 25: ...hen not in use LED Mode Button Press the Mode Button to adjust LED light system from Automatic Color Changes to Individual Colors 1 Auto cycle Rapid 2 Auto cycle Gradual 3 Pause Auto cycle 4 Deep Blue...

Page 26: ...oper and dangerous operation Verify proper operation after servicing WIRING YELLOW RED BLACK BLACK BLACK RED BLACK LED STRIP LED STRIP TRANSFORMER CONTROL MODULE BLACK BLACK BLACK R11931 LEFT BUTTON B...

Page 27: ...n abrasive stainless steel cleaner immediately WARNING Do not use Ammonia based or abrasive cleaners on glass Do not attempt to clean glass when glass is hot PERIODIC CLEANING Refer to parts diagram f...

Page 28: ...n and or replace thermocouple 6 Burner does not stay lit a Burnerorificeclogged Cleanburnerorreplacemainburner orifice b Inlet gas pressure is too low Contact qualified service person 7 If burning at...

Page 29: ...be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number an...

Page 30: ...SEMBLY SUPPLY 1 1 20 P271 FITTING ORIFICE 1 1 21 R10808 AIR SHUTTER STAINLESS 1 1 22 P279 ORIFICE 14 1 0 22 P256 ORIFICE 41 0 1 23 B101848 GAS CONTROL KNOB 1 1 24 R7195 CONNECTOR BRASS MALE 1 1 25 R11...

Page 31: ...35008 1 0515 Page 31 OLL60FP PARTS VIEW 5 4 5 17 16 14 15 4 27 26 25 24 23 19 10 10 12 21 20 18 3 7 8 9 6 28 29 22 30 32 31 11 1 34 35 35 37 38 36 13 2 39 33 33...

Page 32: ...20 P271 FITTING ORIFICE 1 1 21 R10808 AIR SHUTTER STAINLESS 1 1 22 P279 ORIFICE 14 1 0 22 P256 ORIFICE 41 0 1 23 B101848 GAS CONTROL KNOB 1 1 24 R7195 BRASS CONNECTOR MALE 1 1 25 R11916 VALVE LP MANU...

Page 33: ...35008 1 0515 Page 33 OLL60SP PARTS VIEW 27 26 25 24 23 19 10 10 12 21 20 2 3 5 7 8 9 4 28 29 22 4 40 30 2 5 4 17 16 14 15 3 6 32 31 34 35 35 33 11 34 4 18 1 37 38 13 36 39 33...

Page 34: ...35008 1 0515 Page 34 Fireplace SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Page 35: ...A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might...

Page 36: ...t Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact...

Reviews: