background image

13118-7-0408

Page 5

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment 

installed  in  every  dwelling,  building  or  structure  used  in 

whole  or  in  part  for  residential  purposes,  including  those 

owned  or  operated  by  the  Commonwealth  and  where  the 

side wall exhaust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, including but 

not limited to decks and porches, the following requirements 

shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE DETEC-

TORS. At the time of installation of the side wall horizontal 

vented gas fueled equipment, the installing plumber or 

gasfitter shall observe that a hard wired carbon monoxide 

detector with an alarm and battery back-up is installed on 

the floor level where the gas equipment is to be installed. 

In addition, the installing plumber or gasfitter shall observe 

that a battery operated or hard wired carbon monoxide 

detector with an alarm is installed on each additional 

level  of  the  dwelling,  building  or  structure  served  by 

the side wall horizontal vented gas fueled equipment. It 

shall be the responsibility of the property owner to secure 

the services of qualified licensed professionals for the 

installation of hard wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an 

attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the 

next adjacent floor level.

 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installa-

tion, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, 

however, that during said thirty (30) day period, a 

battery operated carbon monoxide detector with an 

alarm shall be installed.

2.  APPROVED  CARBON  MONOXIDE  DETECTORS. 

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 

and be ANSI/UL 2034 listed and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be 

permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally 

vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) 

inch in size, “

GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS”.

4.  INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall 

not approve the installation unless, upon inspection, the 

inspector observes carbon monoxide detectors and signage 

installed in accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The  equipment  listed  in  Chapter  10  entitled 

“Equipment Not Required To Be Vented” in the 

most current edition of NFPA 54 as adopted by 

the Board; and 

 

 

2.  Product Approved side wall horizontally vented 

gas  fueled  equipment  installed  in  a  room  or 

structure separate from the dwelling, building or 

structure used in whole or in part for residential 

purposes. 

 

(c)  MANUFACTURER  REQUIREMENTS  -  GAS 

EQUIPMENT VENTING SYSTEM PROVIDED. 

When the manufacturer of Product Approved side 

wall horizontally vented gas equipment provides a 

venting system design or venting system components 

with the equipment, the instructions provided by the 

manufacturer for installation of the equipment and 

the venting system shall include:

 

 

1.  Detailed instructions for the installation of the 

venting  system  design  or  the  venting  system 

components; and

 

 

2.  A complete parts list for the venting system design 

or venting system. 

 

(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instruc-

tions shall remain with the appliance or equipment 

at the completion of the installation. 

Summary of Contents for DV-55T-1

Page 1: ...eath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas sup...

Page 2: ...r Massachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Maintenance Suggestions 15 How to Order Repair Parts 16 Parts List 16 Parts View 17 Service Notes 18 19 TABLE OF CONTENTS ...

Page 3: ... control compartments burners and circulating air passageways of the appliance be kept clean DO NOT put anything around the furnace that will obstruct the flow of combustion and ventilation air DOkeeptheapplianceareaclearandfreefromcombustible material gasoline and other flammable vapors and liquids DO examine venting system periodically and replace damaged parts DO make a periodic visual check of p...

Page 4: ...ights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstal...

Page 5: ...quiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall ...

Page 6: ...tilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term qualified agency means any indi vidual firm corporation or company which either in person or through a representative is engaged in and is responsible for a the installation or replacement of gas piping or b the connection installation repair or servicing of equipment who i...

Page 7: ...e to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing It is required by the National Fuel Gas Code that a drip line be in...

Page 8: ...from the center of the vent cap to the nearest outside corner or obstruction is 24 inches The vent terminal of a direct vent appliance with an input over 50 000 BTU per hour shall be located at least 12 inches from any opening through which flue gases could enter a building The bot tom of the vent terminal and the air intake shall be located at least 12 inches above grade WARNING The nearest point ...

Page 9: ...provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall as shown in Figure 7 1 Locate and cut the 5 1 2 square opening in the cabinet side using the template from the kit exposing the inner liner knock out 2 Remove the knock out 3 Using the inner...

Page 10: ...left and right side panels A three prong grounding plug assembly is located within the control compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1 Disconnect nylon cap on 3 plug assembly from nylon plug on wiring harness Remove 3 plug assembly from control c...

Page 11: ...isturbs the wind on one side of the air inlet section will result in back pressure on the flue section smothering the flame and eventual pilot outage When the vent cap is to be installed on siding or it appears that a projection within 6 of any side of the air inlet section could shield the air inlet section the entire vent should be supported away from the wall at least the distance of the projecti...

Page 12: ...electric power to the appliance 15 Set thermostat to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORELIGHTINGsmellallaroundtheap...

Page 13: ...v ing the burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air pressure The correct pilot flame Figure 12 will be blue extending past the thermocouple The flame will surround the thermocouple just below the tip Natural gas pilots require adjusting when the inlet gas...

Page 14: ...can be purchased plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can bepluggedintotheadapterandbeelectricallygrounded A7 8 hole is provided in the junction box for use with a conduit connector if local codes require this type of protection Thermostat Installation The thermostat should be ins...

Page 15: ...nace is first installed or was off all summer the pilot flame may be too lean to ignite on the first few trials Turn the controlvalveknobtopilotpositionanddepresstheredresetbutton Holding the button down continually to bleed the line 1 Use lighter rod to light pilot with a match 2 Use the piezo ignitor at 30 second intervals until it lights If Electrode Does Not Produce Spark 1 Check wire connections...

Page 16: ... a Part Number When ordering parts first obtain the Model Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of Gas Propane or Natural Do not order bolts s...

Page 17: ...13118 7 0408 Page 17 PARTS VIEW ...

Page 18: ...13118 7 0408 Page 18 SERVICE NOTES ...

Page 19: ...13118 7 0408 Page 19 SERVICE NOTES ...

Page 20: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer www empirecomfort com ...

Reviews: