39892-4-0719
Page 6
Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one (1) ounce (30ml) of water for
every 1,000 Btu (.3KW's) of gas input per hour.
Unvented room heaters must be used as supplemental heat (a
room) rather than a primary heat source (an entire house). In most
supplemental heat applications, the water vapor does not create a
problem. In most applications, the water vapor enhances the low
humidity atmosphere experienced during cold weather.
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used to
help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat source
(an entire house).
This heater shall not be installed in a confined space or unusu
-
ally tight construction unless provisions are provided for adequate
combustion and ventilation air.
A confined space is an area with volume less than 50 cubic feet per
1,000 Btuh of the combined input rates of all appliances drawing
combustion air from that space. Small areas such as equipment
rooms are confined spaces. Furnaces installed in a confined space
which supply heated air to areas outside the space must draw return
air from outside the space through tightly sealed return air ducts. A
confined space must have 2 openings into the space for combus
-
tion air. One opening must be within 12 inches of the ceiling and
the other must be within 12 inches of the floor. The required sizing
of these openings is determined by whether inside or outside air is
used to support combustion, the method by which the air is brought
to the space (vertical or horizontal duct) and by the total input rate
of all appliances in the space.
The following example is for determining the volume of a typical
area in which the BF-20W may be located and for determining if
this area fits the definition of an unconfined space.
The input of the BF-20W is 20,000 Btu per hour. Based on the 50
cubic feet per 1,000 Btu per hour formula, the minimum area that is
an unconfined space for installation of the BF-20W is 1,000 cubic
feet, 50 cubic feet x 20 = 1,000 cubic feet. To determine the cubic
feet of the area in which the BF-20W is to be installed, measure the
length, width and height of the area. example: The area measures
16 feet in length, 8 feet in width and 8 feet in height, the area is
1,024 cubic feet. The BF-20W can be installed in this unconfined
space with no requirement to provide additional combustion and
ventilation air.
WARNING
If the area in which the heater may be operated is smaller
than that defined as an unconfined space or if the building is
of unusually tight construction, provide adequate combus-
tion and ventilation air by one of the methods described in
the National Fuel Gas code, aNSI Z223.1/NFPa 54, air for
combustion and Ventilation, or applicable local codes.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If the heater is installed in a building of unusually tight construction,
adequate air for combustion, ventilation and dilution of flue gases
shall be provided in accordance with AnSI Z223.1/nFPA54.
WARNING
This heater shall not be installed in a room or space unless
the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code,
aNSI Z223.1/NFPa 54, the
International Fuel Gas Code, or
applicable local codes."
WaTer VaPor: a By-ProDucT oF uNVeNTeD rooM HeaTerS
PROvISIONS FOR ADEqUATE COMBUSTION & vENTILATION AIR