Check all local codes for requirements, especially for the size and 

type of gas supply line required.

Recommended Gas pipe Diameter

Pipe Length

Schedule 40 Pipe

Inside Diameter

Tubing, Type L 

Outside Diameter

Nat.

L.P.

Nat.

L.P.

0-10 feet

0-3 meters

1/2”

12.7mm

3/8”

9.5mm

1/2”

12.7mm

3/8”

9.5mm

10-40 feet

4-12 meters

1/2”

12.7mm

1/2”

12.7mm

5/8”

15.9mm

1/2”

12.7mm

40-100 feet

13-30 meters

1/2”

12.7mm

1/2”

12.7mm

3/4”

19mm

1/2”

12.7mm

100-150 feet

31-46 meters

3/4”

19mm

1/2”

12.7mm

7/8”

22.2mm

3/4”

19mm

Note: 

Never use plastic pipe. Check to confirm whether your local 

codes allow copper tubing or galvanized.

Note:

 Since some municipalities have additional local codes, it is 

always best to consult your local authority and installation code.

Installing a New Main Gas Cock 

Each appliance should have its own manual gas cock.

A  manual  main  gas  cock  should  be  located  in  the  vicinity  of 

the unit. Where none exists, or where its size or location is not 

adequate, contact your local authorized installer for installation 

or relocation.
Compounds used on threaded joints of gas piping shall be resistant 

to the action of liquefied petroleum gases. The gas lines must be 

checked for leaks by the installer. This should be done with a soap 

solution watching for bubbles on all exposed connections, and if 

unexposed, a pressure test should be made. 

never use an exposed flame to check for leaks. Appliance must 

be disconnected from piping at inlet of control valve and pipe 

capped or plugged for pressure test. Never pressure test with 

appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas 

line upstream of the gas control to aid in servicing. It is required 

by the National Fuel Gas Code that a drip line be installed near 

the gas inlet. This should consist of a vertical length of pipe tee 

connected into the gas line that is capped on the bottom in which 

condensation and foreign particles may collect.
The use of the following gas connectors is recommended:

—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-

ing and Fittings

—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority 

having jurisdiction. The state of Massachusetts requires that a flex

-

ible appliance connector cannot exceed three feet in length.

pressure Testing of the Gas Supply System

1.   To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 

plugged tapping, accessible for test gauge connection, must 

be placed immediately upstream of the gas supply connection 

to the appliance.

2.  The  appliance  and  its  individual  shutoff  valve  must  be 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess of 

1/2 psig (3.5 kPa).

3.   The appliance must be isolated from the gas supply piping 

system by closing its individual manual shutoff valve during 

any pressure testing of the gas supply piping system at test 

pressures equal to or less than 1/2 psig (3.5 kPa).

Figure 7

Attention!

 If one of the above procedures results in pressures in 

excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 

it will result in a hazardous condition.

Checking Manifold pressure

(A)VFD26F(M,p)3 

Natural gas will have a manifold pressure of 

approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. 

(.423kPa) for minimum input at the pressure regulator outlet with 

the inlet pressure to the pressure regulator from a minimum of 5.0" 

w.c. (1.120kPa) for the purpose of input adjustment to a maximum 

of 10.5" w.c. (2.614kPa). 

(A)VFD26F(M,p)2

 Natural gas will have a manifold pressure of 

approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet 

with the inlet pressure to the pressure regulator from a minimum 

of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a 

maximum of 10.5" w.c. (2.615kPa). 

(A)VFD26F(M,p)3

  Propane  gas  will  have  a  manifold  pressure 

approximately  10.0"w.c.  (2.49kPa)  for  maximum  input 

or  6.3"w.c.  (1.568kPa)  for  minimum  input  at  the  pressure 

regulator outlet with the inlet pressure to the pressure regulator 

from  a  minimum  of  11.0"w.c.  (2.739kPa)  for  the  purpose 

of  input  adjustment  to  a  maximum  of  13.0"w.c.  (3.237kPa).  

(A)VFD26F(M,p)2

  Propane  gas  will  have  a  manifold  pressure 

approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet 

with the inlet pressure to the pressure regulator from a minimum 

of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a 

maximum of 13.0"w.c. (3.237kPa). 

GAS SUPPLY

Summary of Contents for VFD26FM series

Page 1: ...per hour Refer to page 8 WARNING If not installed operated and main tained in accordance with the manufacturer s in structions this product could expose you to sub stances in fuel or from fuel combus...

Page 2: ...ERS ROCK WOOL 16 OPERATION INSTRUCTIONS FLAME APPEARANCE 16 A VFD26FP3L10 LIGHTING INSTRUCTIONS 17 A VFD26F M P 3 LIGHTING INSTRUCTIONS 18 A VFD26F M P 2 LIGHTING INSTRUCTIONS 19 PILOT FLAME CHARACTER...

Page 3: ...e hazard of high surface temperature and should stay away to avoid burns or clothing ignition Young childrenshould becarefullysupervisedwhen they are in the same room with the appliance Do not place c...

Page 4: ...ight pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or...

Page 5: ...gas company before changing spud orifice size Warning Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage Instructions to Installer 1 Installer m...

Page 6: ...own in Figure 2 for corner rough opening Be sure to provide gas line for fireplace and electrical power for optional blower assembly 1 Attach two 2 nailing flanges to firebox sides with two 2 10 x 1 2...

Page 7: ...E OPENING JUNCTION BOX ASSEMBLY GAS LINE OPENING J I K B C G A D E Figure 4 A VFD26 Series Dimensions Index Letter Dimension A 30 1 4 768mm B 30 762mm C 13 1 8 333mm D 18 1 8 460mm E 26 660mm G 25 635...

Page 8: ...rmostat FREC Electric Remote Control FWS 1 Wall Switch TMV Wall Thermostat Millivolt Reed Switch TRW Wireless Remote Wall Thermostat Water vapor is a by product of gas combustion An unvented room heat...

Page 9: ...e volume is less than 50 cubic feet per 1 000 Btu per hour 4 8m3 per kw of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not l...

Page 10: ...e extra fresh air by using ventilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one with 12 of the floor Connect these items directly to the outdoorsors...

Page 11: ...tors of Other Than All Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction The state of Massachusetts requires that a flex ible appliance connector c...

Page 12: ...rances from the top of the fireplace opening to the ceiling should not be less than 36 inches Mantel Clearances for Built in Installation Figure 9 Do not attach combustible material to the mantel of y...

Page 13: ...Remove shrink wrap and logs from fireplace 6 Place back base and fireplace in desired location 7 Connect gas line and electrical wiring at this time in accor dance with local codes 8 Place mantel ass...

Page 14: ...ogs per the Log Placement Instructions See Page 15 14 Install hood See Page 22 9 Attach mantel assembly to studs in the wall through the back brace using two 2 3 drywall screws provided 10 Slide front...

Page 15: ...This step is optional for A VFD26FP3L10 log sets Place front twig 5 onto 1 log and flat area on 3 log The bottom of the front twig is to be placed behind the grate tang that is second from the left At...

Page 16: ...burner as well as the main flame should be visually checked as the log set is installed In normal operation at full rate after 10 to 15 minutes the flame appearance should be sets of yellow flames NOT...

Page 17: ...r assembly if applicable 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot b...

Page 18: ...able 3 Set REMOTE OFF ON switch to OFF 4 Turn off all electric power to the appliance if applicable 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from PILOT...

Page 19: ...liance 1 Set thermostat gas control knob to lowest setting 2 Turn off all electric power to appliance if service is to be performed if applicable Lighting Instructions 7 Turn gas control knob counterc...

Page 20: ...Troubleshooting page 25 Cleaning and Maintenance Pilot Oxygen Depletion Sensor Pilot When the pilot has a large yellow tip flame clean the Oxygen Depletion Sensor as follows 1 Clean the ODS pilot by...

Page 21: ...FF is the OFF position PILOT is the PILOT position A VFD26F M P 3 Max 20 000 BTU HR Min 14 000 BTU HR A VFD26FP3L10 Max 10 000 Min N A A VFD26F M P 2 Main Burner Operation The gas control modulates fr...

Page 22: ...fireplace Attach top frame to fireplace Use two 2 8 x 1 2 Phillips screws for top frame 5 Replace bottom louver 6 Replace top louver 3 PIECE FRAME KIT SIDE TRIM Figure 21 HOOD INSTRUCTIONS 1 Remove up...

Page 23: ...burner assembly Note Do not let remote control receiver come in contact with burner assembly On circulating vent free firebox install remote control receiver behind bottom louver Refer to remote contr...

Page 24: ...ELECTRICAL CODE ANSI NFPA 70 LATEST EDITION A factory installed junction box is located on the lower right side of the fireplace Wiring must be fed to the junction box and attached to the receptacle t...

Page 25: ...ct Replace gas regula tor 7 ODS pilot lights but flame goes out when control knob is released a Control knob not fully pressed in Press in control knob fully b Control knob not pressed in long enough...

Page 26: ...N S R3435 WIRE ASSEMBLY A VFD26F M P 3LP PART NUMBERS 10 R3623 PILOT ASSEMBLY 11 21590 PILOT BRACKET 14 R9022 BURNER TUBE 16 P182 ORIFICE 19 23493 TUBING ASSEMBLY 21 R3625 VALVE 23 23496 TUBING ASSEM...

Page 27: ...e 27 PARTS VIEW 5 PIECE LOG Y ASSEMBL MILLIVOLT VALVE Y ASSEMBL THERMOSTATIC VALVE Y ASSEMBL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 21 22 23 23 24 25 26 27 28 29 29 30 31 18 32 33...

Page 28: ...of fireplace The magnets on the bottom of speed control will sufficiently hold the speed control in place 13 Attach fan control bracket to upper right side of firebox with one 10 x 1 2 hex screw prov...

Page 29: ...r Kit 110 VOLT AC JUNCTION BOX WHITE SPEED CONTROL FAN SWITCH GROUND BLACK FAN WHITE BLACK SWITCH BRACKET FBBX Wiring Diagram FBBX BLOWER KIT EXTENSION INSTALLATION INSTRUCTIONS cont FBB4 OPTIONAL VAR...

Page 30: ...e 1 side panel into firebox 5 Align clearance hole on brick panel bracket with screw hole in the left or right interior top of firebox Use two 2 10 x 1 2 screws to attach brick panel bracket to interi...

Page 31: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Page 32: ...23466 4 0509 Page 32 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62222 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: