Empire Comfort Systems DVP30CA30B-N1 Installation Instructions And Owner'S Manual Download Page 5

24032-2-1008

Page 5

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment 

installed  in  every  dwelling,  building  or  structure  used  in 

whole  or  in  part  for  residential  purposes,  including  those 

owned  or  operated  by  the  Commonwealth  and  where  the 

side wall exhaust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, including but 

not limited to decks and porches, the following requirements 

shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE DETEC-

TORS. At the time of installation of the side wall horizontal 

vented gas fueled equipment, the installing plumber or 

gasfitter shall observe that a hard wired carbon monoxide 

detector with an alarm and battery back-up is installed on 

the floor level where the gas equipment is to be installed. 

In addition, the installing plumber or gasfitter shall observe 

that a battery operated or hard wired carbon monoxide 

detector with an alarm is installed on each additional 

level  of  the  dwelling,  building  or  structure  served  by 

the side wall horizontal vented gas fueled equipment. It 

shall be the responsibility of the property owner to secure 

the services of qualified licensed professionals for the 

installation of hard wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an 

attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the 

next adjacent floor level.

 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installa-

tion, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, 

however, that during said thirty (30) day period, a 

battery operated carbon monoxide detector with an 

alarm shall be installed.

2.  APPROVED  CARBON  MONOXIDE  DETECTORS. 

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 

and be ANSI/UL 2034 listed and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be 

permanently mounted to the exterior of the building at a 

minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally 

vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) 

inch in size, 

“GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS”.

4.  INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall 

not approve the installation unless, upon inspection, the 

inspector observes carbon monoxide detectors and signage 

installed in accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The  equipment  listed  in  Chapter  10  entitled 

“Equipment Not Required To Be Vented” in the 

most current edition of NFPA 54 as adopted by 

the Board; and 

 

 

2.  Product Approved side wall horizontally vented 

gas  fueled  equipment  installed  in  a  room  or 

structure separate from the dwelling, building or 

structure used in whole or in part for residential 

purposes. 

 

(d)  MANUFACTURER  REQUIREMENTS  -  GAS 

EQUIPMENT  VENTING  SYSTEM  NOT  PRO-

VIDED. When the manufacturer of a Product Ap-

proved  side  wall  horizontally  vented  gas  fueled 

equipment does not provide the parts for venting the 

flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the 

manufacturer:

 

 

1.  The referenced “special venting system” instruc-

tions  shall  be  included  with  the  appliance  or 

equipment installation instructions; and

 

 

2.  The “special venting systems” shall be Product 

Approved by the Board, and the instructions for 

that system shall include a parts list and detailed 

installation instruction.

 

(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instruc-

tions shall remain with the appliance or equipment 

at the completion of the installation. 

Summary of Contents for DVP30CA30B-N1

Page 1: ...30CA30 B F M S W N 1 DVP30CA30 B F M S W P 1 Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to l...

Page 2: ...tem Identi cation 16 Framing and Finishing 17 18 Horizontal Termination 18 Vertical Termination 19 20 Log Placement 21 Operating Guidelines 22 Lighting Instructions 23 Pilot Flame Characteristics 24 M...

Page 3: ...ace is temperedglass Iftheglassiscrackedordamagedin any way it should be replaced only with a complete glass frame assembly from Empire See parts list on Page 30 for ordering DONOTusethis replaceifany...

Page 4: ...heodorantinescapedgascanadsorborabsorbontoorintowalls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratif...

Page 5: ...ply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior of the building at a minimum height of eight 8 feet...

Page 6: ...in such work familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction The installation must conform with local codes or in the absence of...

Page 7: ...6DVA E90B DVKVP Direct Vent Kit for Vertical Run 2 46DVA 48B 46DVA DC 46DVA F6 46DVA SC 46DVA FS 46DVA VCH Accessories TMV Millivolt Wall Thermostat Reed Switch FRBC Battery Operated Remote Control FR...

Page 8: ...This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect When using copper or ex connector...

Page 9: ...rs 45 angle to Wall 4 101 6 mm Floor 0 0 mm Installation on Rugs and Tile This appliance must be installed on a at solid continuous surface e g wood metal concrete This may be the oor or it may be rai...

Page 10: ...te must be used above 10 feet Maximum horizontal run from appliance outlet 12 feet 3 66 m Maximum vertical rise and horizontal run is a combined total of 25 feet 7 62 m Maximum elbows 2 90 for the sec...

Page 11: ...ide and bottom Cutting the Hole Figure 7 After the appliance has been positioned in its permanent location the hole through the exterior wall of the house can be cut This hole needs to be 10 high x 10...

Page 12: ...2 Remove cast iron front and carefully set aside 3 Carefully remove glass door 4 Remove the log shelf by removing the 2 screws securing the log shelf to the wall 5 Loosen the upper 2 screws of both ai...

Page 13: ...ack down locking the air shutter in place Be sure that the air shutter is the same distance from the burner ori ce on both sides of the air shutter for proper burner t up 10 Carefully replace the burn...

Page 14: ...ng Routes and Components Important It is always best to locate the appliance in such a way that minimizes the number of offsets and horizontal vent length Figure 14 Since it is very important that the...

Page 15: ...e of the regulator I Clearance to service regulator vent outlet 6 feet 1 83 m minimum J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 i...

Page 16: ...hes The vent pipe is now locked together Continue adding components per the pre planned vent system con guration Be certain that each succeeding vent component is securely tted and locked into the pre...

Page 17: ...usly cut Secure with nails or screws Continue the vent run through the restops See Figure 19 Figure 19 Vertical runs of this system which pass through ceilings require the use of ONE 1 ceiling restop...

Page 18: ...provided Before attachment of the termination run a bead of silicone sealant rated above 250 F on its outside edge too so as to make a seal to that exterior wall NOTE Wood screws can and should be rep...

Page 19: ...are as follows 1 Check areas of the venting system which are exposed to the elements for corrosion These will appear as rust spots or streaks and in extreme cases holes These components should immedi...

Page 20: ...bustiblematerials includinginsulation to the vent system are maintained Vertical Through the Roof Applications Your Gas Fireplace has been approved for a Vertical installations up to 25 feet of vent r...

Page 21: ...on the groove in the left front log 12 Place right twig onto right side pin on rear log with toe resting all the way to the right on the right front log 13 Align and place top of glass frame over lip...

Page 22: ...to OFF Standing Pilot Operation 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found attached to the appliance CAUTION Duringtheinitialpur...

Page 23: ...a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORELIGHTINGsmellallaroundtheappliancearea for gas Be sure to smell next to the oor because some ga...

Page 24: ...mopilejustbelow the tip A slight yellow ame may occur where the pilot ame and main burner ame meet The incorrect pilot ame is not touching the thermocouple or thermopile This will cause the thermocoup...

Page 25: ...epersonshouldcleandust lint and any light accumulation from the logs and the rebox area An extra soft brush should be used on the logs as they are extremely fragile a vacuum cleaner may be used on the...

Page 26: ...en wires female push ons attach to the ON OFF REMOTE switch At the opposite end of the wire harness the black and green wires female push ons attach to the gas valve An additional green wire and the r...

Page 27: ...24032 2 1008 Page 27 Wiring Diagram Figure 34 WIRING continued...

Page 28: ...ass frame assembly on a non abrasive surface The exterior of the glass frame assembly should be facing the non abrasive surface 7 Insert a putty knife between glass and bottom corners on frame Careful...

Page 29: ...ivolts minimum while holding thevalveknobdepressedtothepilotposition withthepilot lit and the ON OFF switch in the OFF position Replace the faulty thermopile if the reading is below the speci ed minim...

Page 30: ...UE OUTLET GASKET 3 REQUIRED 5 24176 AIR DROP ASSEMBLY 6 R 9678 AIR DROP ASSEMBLY TRANSITION GASKET 7 24015 AIR DROP TRANSITION 8 R 9679 FIREBOX TRANSITION GASKET 9 17379 BLOW PLATE BRACKET 2 REQUIRED...

Page 31: ...24032 2 1008 Page 31 PARTS VIEW 1 9 4 2 3 4 6 4 8 10 11 12 14 15 16 28 29 31 36 37 38 39 40 41 42 43 44 45 30 17 18 19 20 21 22 24 25 26 27 32 34 35 23 13 33 5 7 29 47 9 46...

Page 32: ...IGHT 8 R 9694 CASTING DOOR LEFT 9 24042 FIREBOX SUPPORT BRACKET 2 REQUIRED 11 R 9549 CASTING LEG B 12 R 9548 CASTING LEG A PORCELAIN BLACK 1 R 9570 TOP INSERT RIGHT 2 R 9569 TOP INSERT LEFT 3 R 9568 C...

Page 33: ...24032 2 1008 Page 33 1 2 8 3 4 5 6 7 9 9 10 10 10 10 12 11 11 12 CASTING PARTS VIEW...

Page 34: ...o casting before fully tightening bolts as shown in Figure 37 9 Replace cast iron or stone inlay inserts into casting top Note Be sure to remove side shelf supports prior to removing cast iron top to...

Page 35: ...lot 6 Route fan control wires through rectangular notch on wire channel left 7 Attach 1 4 push on terminal from blue wire on the fan control to the AUTO top tab on the switch OPTIONAL BLOWER INSTALLAT...

Page 36: ...ly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug For an ungrounded receptacle an adapter which has two prongs and a wire for grounding can be...

Page 37: ...nt Then determine the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Stove Model Number Sto...

Page 38: ...24032 2 1008 Page 38 SERVICE NOTES...

Page 39: ...facing the front of the direct vent replace the minimum clearances to combustible construction material are the following Top of appliance ceiling 36 inches Heater Corners 45 angle to Wall 4 inches Re...

Page 40: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Reviews: