62
Software index
Emotron AB 01-3990-11r3
2- Manual/Automatic Restart Modes
Function
Code no.
Description
Range/Code
Factory
setting
Re-
marks
2-00
Momentary Power
Loss and Restart
0000: Momentary power loss
and restart disable
0001: Momentary power loss
and restart enable
0002: Momentary power loss
and restart enable while CPU is
operating. (According to the
capacity of DC power)
0000
2-01
Momentary Power
Loss Ride-Thru Time
(Seconds)
0.0 to 2.0
0.5
2-02
Auto Restart Delay
Time (Seconds)
0.0 to 800.0
0.0
2-03
Number of Auto
Restart Attempts
0 to 10
0
2-04
Auto Restart
Method
0000: Enable Speed Search
0001: Normal Start
0000
2-05
Direct Running After
Power Up
0000: Enable Direct running
after power up
0001: Disable Direct running
after power up
0001
*8
2-06
Delay-ON Timer (s)
0.0 to 300.0
0.0
2-07
Reset Mode Setting
0000: Enable Reset only when
Run command is Off
0001: Enable Reset when Run
command is On or Off
0000
2-08
Kinetic Energy
Back-up
Deceleration Time
0.0: Disable
0.1 to 25.0: KEB Deceleration
Time
0.0
Summary of Contents for VSC 48-009
Page 1: ...Emotron VSC Variable Speed Drive Quick Setup Guide Multilingual...
Page 3: ...Emotron AB 01 3990 11r3...
Page 15: ...14 Anmerkungen zur Verkabelung Emotron AB 01 3990 11r3...
Page 38: ...Emotron AB 01 3990 11r3 Programmierungsanweisungen und Men liste 37...
Page 130: ...Emotron AB 01 3990 11r3 Localizaci n de aver as y mantenimiento 129...
Page 142: ...Emotron AB 01 3990 11r3 Kabelaansluitingen 141...
Page 163: ...162 Programmeringsinstructies en Menulijst Emotron AB 01 3990 11r3...
Page 182: ...Emotron AB 01 3990 11r3 Kabeldragning 181...
Page 209: ...208 Fels kning och underh ll Emotron AB 01 3990 11r3...