
13
Note:
dis = disable
Min
Default
ENGINE PLANT BATTERY (
)
Engine->Plant battery
Max
Battery Undervolts Shutdown
Battery Undervolts Warning
Battery Undervolts Warning Reset
Battery Undervolts Volts Delay
Battery Overvolts Shutdown
Battery Overvolts Warning
11.0
Battery Overvolts Warning Reset
6.0(dis)
6.0(dis)
30.0
30.0
11.5
6.0
1.0
0.0 120.0
29.0
28.5
Charge Alternator Warning
dis
30.0
30.0
30.0
6.0 30.0
Battery Overvolts Delay
1.0
0.0 120.0
30.0
6.0(dis)
6.0(dis)
6.0(dis)
Under volt shutdown
Under volt warning
Under volt reset
Under volt delay
Over volt shutdown
Over volt warning
Over volt reset
Over volt delay
Alt. chg. warning
Unit
V
Z
V
Z
V
Z
V
Z
V
Z
V
Z
Sec
Sec
V
Z
dis
dis
CANBUS ECU (
)
Engine->CanBus ECU
Baud rate
J1939 ECU type
Device address
SPN version
Min
Default
Unit
Max
0
7
4
31
0
0
255
17
1
3
1
kBaud
ECU remote control
Speed control enable
Oil pres cont. enab
Temp. control enable
ENABL
Device Address
0(dis)
SPN version
ECU Remote Control via J1939
Speed Control via J1939
Oil Pressure Control via J1939
Coolant Temperature Control via J1939
Speed correction
50
Speed Correction Value
%
0
100
Speed set point
1500
1500 1800
/
Speed Set Point Selection
RPM
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
DISBL
Baud Rate:
0: 20,
1: 50,
2: 100, 3: 125,
4: 250, 5: 500, 6: 800, 7: 1.000
J1939 ECU Type Selection:
0 - Disable
1 - Standard
2 - Volvo EMS1
3 - Volvo EMS2
4 - Volvo EMS2b
5 - Volvo EDC3
6 - Volvo EDC4
7 - Deutz EMR2
8 - Deutz EMR3
9 - Perkins 1300
10 - Perkins ADEM3
11 - Perkins ADEM4
12 - Scania S6
13 - MAN MFR
14 - Cummins ISB
15 - Cummins CM570
16 - Cummins CM850
17 - Cummins CM2150E
18 - Cummins CM2250
19 - Detroit DDEC
20 - John Deere
21 - MTU ADEC
22 - MTU ECU8
23 - MTU ECU8 SAM
24 - Yuchai
25 - Kubota
26 - Baudouin WISE10B
27 - Baudouin WISE15
28 - Perkins 1600
29 - Perkins A4E2
30 - Perkins A5E2
31 - Perkins A5E2v2