EMKO TRANS-AMF Manual Download Page 11

11

9999

9999

9999

9999

9999

9999

kVA

kVA

kVA

kVA

0

0(dis)

0

0

0(dis)

0

Min

Default

Max

Generator Under

Set

Power

Generator Under

Pre-Alarm

Power

Generator Under

Pre-Alarm Reset

Power

Generator Over

IDMT Alarm

Power

Generator Over

Set

Power

Generator Over

Pre-Alarm

Power

0

5

Generator Over

Pre-Alarm Reset

Power

kVA

kVA

Unit

Generator Over

Delay Time

Power Action

Generator Over Load Step 1

Generator Over Load Step 1 Reset

Generator Over

1

Delay Time

Load Step

Action

Reverse Power Set

Reverse Power Action Delay Time

0

0

0

0(dis)

0

-9999

0(dis)

0

99

9999

9999

3

999.9

0

3

99

2

9999

9999

0(dis)

30.0

0

0(dis)

2

Sec

KVA

KVA

Sec

kW

Sec

dis

0

0

dis

Reverse Power Actions

Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator

Followed By Shutdown After Cooling)

Shutdown (Alarm And Shutdown)

0 -
1 -
2 -

3 -

Under

set

power

Under

prealarm

power

Under

reset

power

Over

IDMT alarm

power

Over

set

power

Over

prealarm

power

Over

reset

power

Over act. delay time
Over load step 1
Over load step 1 rest
Over load step 1 act.

Over load step 1 dly.

Reverse power set
Reverse power act.

Rv.pow.act.delay time

GEN

LEVEL (

)

POWER

Generator->Power level

Generator Under

Delay Time

Power Action

0(dis)

0

3

99

0(dis)

2

Sec

Generator Under

Actions

Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator

Followed By Shutdown After Cooling)

Shutdown (Alarm And Shutdown)

Power

0 -
1 -
2 -

3 -

Under power act.

Under act. delay time

0(dis)

3

0(dis)

Generator Over

Actions

Disable
Warning (Alarm Only, No Shutdown)
Electrical Trip (Alarm/Off Load Generator

Followed By Shutdown After Cooling)

Shutdown (Alarm And Shutdown)

Power

0 -
1 -
2 -

3 -

Over power act.

ENABL/DISBL

DISBL

Generator Over

Actions

Disable

Warning
Warning

Load Step 1

0 -
1 - Status
2 -

Non-Latching

3 -

Latching

Generator Over Load Step 2

Generator Over Load Step 2 Reset

Generator Over

Delay Time

Load Step 2 Action

0

0

0(dis)

0

9999

9999

3

999.9

9999

9999

0(dis)

30.0

KVA

KVA

Sec

Over load step 2
Over load step 2 rest
Over load step 2 act.

Over load step 2 dly.

Generator Over

Actions

Disable

Warning
Warning

Load Step 2

0 -
1 - Status
2 -

Non-Latching

3 -

Latching

Note:

dis = disable

Summary of Contents for TRANS-AMF

Page 1: ...ins failure Intended for unattended operation it is able to detect failure of any phase of the mains and to start and switch over to a generator if the mains voltage goes outside pre set limits Both a...

Page 2: ...nected to ground only one side Before commissioning the device parameters must be set in accordance with desired use Incomplete or incorrect configuration can cause dangerous stiuations Before beginni...

Page 3: ...Input 2 Sender Common 18 19 17 H L J1939 ECUs 34 33 BATTERY 32 31 30 29 28 High Temperature or Configurable Input 5 Low Oil Pressure or Configurable Input 4 Water Level or Configurable Input 3 Configu...

Page 4: ...PROGRAM Operator setting Technician setting Factory adjustment PROGRAM Operator setting Technician setting Factory adjustment TECHNICIAN SETTING Password 0162 TECHNICIAN SETTING Password 0000 TECHNIC...

Page 5: ...tdown Delay Time GENERATOR VOLT LEVEL Generator level Volt 0 0 10 0 1 0 Sec 75 0 30 0 dis 75 0 75 0 Hz 30 0 dis Min Default Max Generator Under Frequency Pre Alarm Generator Under Frequency Pre Alarm...

Page 6: ...RKING CALENDAR Generator Working calendar 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 23 59 H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H Min H...

Page 7: ...e Selection 7 Min Default Unit BREAKERS System Breakers Max Hardware Breaker Selection Gen Close Breaker Contact Type Gen Close Breaker Relay Type Gen Close Timer 0 Gen Open Breaker Relay Type 0 2 Gen...

Page 8: ...Default Unit PASSWORD SETTINGS System Password settings Max Operator Password Technician Password 0 0 9999 0 9999 0 Operator password Technician password Min Default Unit DEFAULT SETTINGS System Defau...

Page 9: ...r freq prealarm Over freq reset Shutdown delay time Unit GENERATOR LEVEL FREQ Generator level Frequency 75 0 75 0 Hz 30 0 Nominal Alternator Frequency 50 0 43 0 Hz Nominal frequency Under freq shutdow...

Page 10: ...dis 2 AV AV AV 0 0 dis 0 0 dis 0 0 0 dis 9999 9999 9999 3 99 9999 9999 1 dis 5 dis 2 9999 9990 AV AV AV AV AV Sec Sec Sec Generator Under Current Actions Disable Warning Alarm Only No Shutdown Electr...

Page 11: ...lay time Over load step 1 Over load step 1 rest Over load step 1 act Over load step 1 dly Reverse power set Reverse power act Rv pow act delay time GEN LEVEL POWER Generator Power level Generator Unde...

Page 12: ...Sensing Opt Pickup En Dis Flywheel DISBL 1000 All Warnings Are Latched En Dis Changed To Stop Mode On Shutdown Fail Sens opt pickup flywh All warning are latch Stop mode on shutdown ENABL DISBL ENABL...

Page 13: ...55 17 1 3 1 kBaud ECU remote control Speed control enable Oil pres cont enab Temp control enable ENABL Device Address 0 dis SPN version ECU Remote Control via J1939 Speed Control via J1939 Oil Pressur...

Page 14: ...nly No Shutdown 3 Electrical Trip Alarm Off Load Generator Followed By Shutdown After Cooling 4 Shutdown Alarm And Shutdown 2 0 2 0 0 dis 4 Amber warn activation Amber warn actions Sec J1939 Amber War...

Page 15: ...art time on monday 4 Stop time on monday 1 Stop time on monday 2 Stop time on monday 3 Stop time on monday 4 Start time on tues 1 Start time on tues 2 Start time on tues 3 Start time on tues 4 Stop ti...

Page 16: ...on day 4 Satur Exercise Stop Time on day 1 Sun Exercise Stop Time on day 2 Sun Exercise Stop Time on day 3 Sun Exercise Stop Time on day 4 Sun Start time on day 1 fri Start time on day 2 fri Start tim...

Page 17: ...ure shutdown Oil pressure reset Oil pressure prealarm Oil press input type 0 dis 70 Low Temperature Warning C Low temp warning Conf AI1 unit Configurable Analog Input 1 Type 0 dis 0 Not Used Disable 1...

Page 18: ...ime Fuel Filling Maximum Time 30000 Fuel fill alarm reset Fuel consumpt reset Fuel tank capacity Fuel Filling Alarm Reset Fuel Consumption Reset Fuel Tank Capacity NO NO 100 YES NO YES NO 250 0 Sec 0...

Page 19: ...Point 4 Configurable Analog Input 1 Point 5 15 31 49 66 85 101 117 132 149 178 579 404 342 250 179 136 103 77 67 63 10 30 50 70 90 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1300 1300 1300 130...

Page 20: ...ender Point 6 Configurable Analog Input 2 Sender Point 7 Configurable Analog Input 2 Sender Point 8 Configurable Analog Input 2 Sender Point 9 Configurable Analog Input 2 Sender Point 10 Configurable...

Page 21: ...In6 26 1 in 25 in2 3 in3 4 in4 25 in5 25 in6 7 1 in1 2 in2 3 1 in4 5 2 in6 1 in1 0 in2 0 in3 4 in4 0 in5 0 in6 0 in1 2 2 in3 4 2 in5 6 2 in1 0 in2 3 5 in4 5 0 in6 5 in1 3 1 in2 4 0 in5 6 0 If Select F...

Page 22: ...on 6 Simulate Auto Button 7 Simulate Test Button 8 Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Mains Closed Auxili...

Page 23: ...st Button 8 Simulate Manual Button 9 Simulate Start Button 10 Simulate Stop Button 11 Generator Closed Auxiliary 12 Generator Load Inhibit 13 Mains Closed Auxiliary 14 Mains Load Inhibit 15 Auto Resto...

Page 24: ...LATCHED 62 HORN OUTPUT PULSED 63 MASTER AUTO READY 64 CONF AI2 CONTROL 65 LOSS OF MAGNETIC PICK UP SPEED SIGNAL 66 LOW TEMPERATURE 67 MAINTENANCE DUE ALARM 68 MAINS CLOSED AUXILIARY 69 MAINS FAILED TO...

Page 25: ...Conf output 6 CONF EXP OUTPUT 1 Outputs Conf exp output 1 CONF EXP OUTPUT 2 Outputs Conf exp output 2 CONF EXP OUTPUT 3 Outputs Conf exp output 3 CONF EXP OUTPUT 4 Outputs Conf exp output 4 CONF EXP...

Page 26: ...ec Mains Return Delay 5 0 3600 Mains return delay Sec 4 2 8 Expansion Modules IO 1 8 MODULE Expansion modules IO 1 8 Expansion I O Module Selection Disable enable select Min Default Max DISBL ENABL DI...

Page 27: ...me Remote Priority Selection Disable enable select Node ID Working period Early start time Remote priority selct Min Default Max 1 0 00 0 0 dis 2 98 59 250 2 1 1 00 15 dis H Min Sec 0 Disable 1 Priori...

Page 28: ...pment II Normal office or workplace non conductive pollution Continuous 8 to 32 V Peak 36 V Max operating current is 360mA Battery voltage can be 0 VDC for max 50 ms during cranking battery voltage sh...

Page 29: ...Karanfil Sk No 6 16369 BURSA TURKEY Phone 90 224 261 1900 Fax 90 224 261 1912 Relay Outputs Transistor Outputs Approvals Generator contactor relay output 8A 250V Mains contactor relay output 8A 250V C...

Reviews: